Determine failure mode by observing flashing LED status on ignition module.

LED status and probable cause shown below.

* Denotes conditions that may require the water heater to be isolated from the vent

system to determine root cause.

LED status & probable cause

For models with Hot Surface Ignition

LED STATUS

Power & flame

light flashing.

Probable Cause

Supply voltage

polarity.

LED STATUS

Valve light flashing.

Probable Cause

Flame sensor.

(see page 32)

Probable Cause

Hot surface igniter.

(see page 30)

Probable Cause*

Combustion system.

(see page 18)

Probable Cause

Blower.

(see page 25)

Probable Cause*

Exhaust pressure

switch. (see page 27)

LED STATUS

Purge light flashing.

LED STATUS

Only power light

is on and water heater

will not function.

Probable Cause

Thermostat circuit.

(see page 12)

Probable Cause*

Exhaust pressure

switch. (see page 27)

Probable Cause

Vent safety switch.

(see page 36)