Flame sensor testing procedure, Laars heating systems, Warning – LAARS U.H.E. - Service Manual User Manual

Page 32

Advertising
background image

LAARS Heating Systems

Page 32

With flame sensor Disconnected

from ignition module, check

continuity to ground.

Is there continuity to ground?

N

Y

Flame Sensor Testing Procedure

Refer to illustration below, is there

a minimum of 1 micro amp during

1.5 second flame proving period?

Y

N

Is flame sensor free

of oxidation?

Clean or replace

flame sensor with emery

cloth. (see page 33)

N

Is ceramic of flame

sensor cracked?

Replace flame sensor.

(see page 33)

Y

N

Flame sensing circuit OK

Y

Refer to ignition module/control board

illustration.(24 volts should maintain beyond the

1.5 second flame proving period.)

Is there 24 volts AC at locations

P3(2) & P3(5)?

Y

N

Call for

technical support

Replace flame sensor with

gasket and/or wire lead.

(see page 33)

Remove flame sensor from water heater.

Check continuity from tip of flame sensor

to end of wire lead.

Is there continuity?

N

Y

WARNING

120 volt potential exposure. Use caution

making voltage checks to avoid

personal injury. Flame sensor may be

too hot to handle, take necessary

precautions

32

Flame

sensor

terminal

Volt meter set to

Micro amps setting

(µA)

Meter

probe

Meter

probe

Flame sensor

terminal on

ignition module.