Step 1.

Position main power switch to “OFF”.

Step 2.

Disconnect (unplug) water heater from

120 volt power source.

Step 3.

Turn off gas supply to water heater.

Step 4.

Un-latch and remove surround cover from top of

heater.

Step 5.

From the gas valve, disconnect the gas

connection, PVC venting, Silicone tubing

and wire harness.

Step 6.

Disconnect wire harnesses flame sensor and

Blower. Disconnect wire harness from hot surface

igniter.

Step 7.

Remove the 5 bolts (½" socket)

holding the burner mounting insert

in place.

Step 8.

Carefully remove combustion assembly

with gasket from water heater.

Step 9.

See next page for combustion system installation procedure.

Combustion System Removal Procedure

WARNING

120 volt potential exposure. Isolate the

appliance and reconfirm power is

disconnected using a multi-meter.

WARNING

Heater components may be HOT when performing the following steps in this procedure.

Take necessary precaution to prevent personal injury.

Gas valve

wire harness

Gas

connection

PVC vent

connection

Burner mounting

insert

Burner mounting

screw

(Total of 5)

Burner tube

Burner mounting

insert gasket

20