Product Handling - Carefully uncrate the heater. Move in place with a hand truck (Do not use the

venting pipes for handles).
Electrical Requirements - Make sure there is 120 volts line voltage. Line voltage must be properly

polarized. Adequate ground supplied to the heater.
Venting Requirements - All venting must stay within the required lengths and diameter (see table

below). Proper support of the venting pipe is a MUST (every 5ft vertical and 3ft horizontal).

Termination must be located to prevent re-circulation of flue gases. Medium to long sweep 90°

elbows or straight exhaust terminal coupling recommended.
Gas Requirements - Gas piping sized adequately, ¾" or larger to heater or 1" or larger for

UHE100T399 models. Install a properly sized regulator (if unknown, assure an adequate volume of

gas is available). 7" W.C. is required when the unit is running. Gas pressure must stay below 14"

W.C. static pressure. Pressure drops between static pressure and operating flow should be less

than 3" W.C.
Condensate Requirements - Condensate line needs to slope to a drain at a minimum of ¼" per

foot. Make sure the condensate line does not have the potential to freeze. If using more than one

heater and using a common condensate line, make sure the condensate line is properly sized.
Service/Mechanical Room - Provide adequate space for servicing heater. Leave room to get to the

top and bottom pressure switches as well as enough overhead room to remove the anode rods for

servicing (18" min.).

Vent tables

Note: each 3" & 4" 90° Elbow is equivalent to 5 feet of

straight pipe.

Note: each 3" & 4" 45° Elbow is equivalent to 2.5 feet of

straight pipe.

43

Unbalanced Direct Vent Systems

Air intake CAN NOT exceed exhaust

by more than 30 feet

Power Vented Systems

PVC, CPVC

Total length of exhaust piping must not exceed

“Maximum Vent Length”

Shown below

Maximum Vent Length (feet)

Model Number

3"

UHE60T125, UHE100T150

120'

UHE60T150, UHE100T199

UHE60T199

UHE100T300

100'

80'

60'

4"

170'

150'

130'

110'

UHE100T399

50'

100'

Balanced Direct Vent Systems

PVC, CPVC

Total length of intake piping and exhaust piping

added together must not exceed “Maximum

Combined Length” Shown below

Maximum Combined Length (feet)

Model Number

3"

UHE60T125, UHE100T150

120'

UHE60T150, UHE100T199

UHE100T250

UHE100T300

100'

80'

60'

4"

170'

150'

130'

110'

UHE100T399

50'

100'

UHE60T199

80'

130'

UHE100T250

80'

130'