SECTION 2.
Troubleshooting

(Detailed Flow Charts on Page 16-22)

If the burner “locks out” for any reason, the

cause of failure will be displayed by the flashing of one
of the lights.

2A. Code

GREEN “POWER” - Light flashing - control

failure, no light, no power

RED “PURGE” - Light flashing - blower or

stack switch failure or possible flue blockage.

RED “VALVE/FLAME” - Light flashing - valve,

igniter or flame sense failure (combustion related
problem).

Normal Operation.

Note: If the stack switch contacts are closed for

any reason when the blower isn’t operating, a sequence
will not occur and after 45 seconds the control will
“lock out” and the “PURGE” light will flash. If the
stack switch contacts are open and do not close during
purge period, after 5 minutes the control will lock out
and the “PURGE” light will flash. If the boiler does not
operate, the green “POWER” light is on and no
indicator lights are flashing, check for an open vent
TCO, operating control or safety limit switch. For
additional troubleshooting information refer to the
trouble shooting flow charts on the pages that follow.

POWER

ON

THERMOSTAT

CALL FOR HEAT

THERMOSTAT

CALL FOR

HEAT ENDS

STANDBY

PROVE NO

AIRFLOW

PROVE

AIRFLOW

PREPURGE

WARMUP

TRIAL FOR

IGNITION

RUN

POST

PURGE

STANDBY

45

SEC

MAX

5

MIN

MAX

15

SEC

20

SEC

8

SEC

30

SEC

POWER LED

AQUASTAT/AUXILIARY
LIMITS

CIRCULATOR

AIR PROVING SWITCH

COMBUSTION
AIR BLOWER

PURGE LED

IGNITER

PROOF OF FLAME

IGNITER LED

GAS CONTROL

VALVE/FLAME LED

1

3

3

CLOSED

CLOSED

OPEN

2

2 SEC

AP

1 SEC

1

POWER LED BLINKS ONCE WHEN 24V POWER IS APPLIED AND WHEN THE THERMOSTAT CALLS FOR HEAT.

2

ON AS LONG AS CONTROL IS POWERED AND OPERATING PROPERLY.

3

IF EITHER SWITCH OPENS DURING THE RUN CYCLE, BURNER WILL STOP, FOLLOWED BY POSTPURGE.
CIRCULATOR WILL RUN AS LONG AS THERMOSTAT IS CALLING FOR HEAT. BURNER IGNITION SEQUENCE
WILL RESTART IF SWITCH CLOSES.