LAARS Heating Systems

YES

CHECKING INTERNAL PUMP

(YOU MUST COMPLETE PAGE 16 FIRST)

SWITCH POWER ON, GREEN

POWER LIGHT LIGHTS

CALL FOR HEAT EXISTS

(THERE IS 24 VOLTS ON

PINS #7 & #9 ON

'CONTROL' PLUG - CN6)

THERE IS 120 VAC AT

'CIRCULATOR' PLUG-CN5

TURN UP T'STAT OR AQUASTAT OR

CORRECT STAT PROBLEM

NO

YES

NO

YES

SEE TROUBLE SHOOTING

CHART PAGE 16

THERE IS 120 VAC AT PUMP

REPLACE BOILER

CONTROL P/N 2400-224

NO

CORRECT WIRING BETWEEN

PUMP AND CONTROL BOX

NO

MOTOR PUMP RUNS

YES

NO

REPLACE PUMP

PUMP IS PUMPING

YES

PUMP OK

PUMP IS AIR BOUND OR IMPELLER HAS

BROKEN; ELIMINATE AIR OR REPLACE PUMP

NO

YES