LAARS 9600 CB & HWG - Service Manual User Manual

Page 17

Advertising
background image

9600 CB & HWG Service Manual

Page 17

1

2

3

4

5

6

7

8

9

RED

RED

CN6

"CONTROL"

1. SWITCH BOILER OFF
2. UNPLUG 9 PIN "CONTROL" PLUG
3. CHECK FOR CONTINUITY AT BACK OF

"CONTROL" PLUG BETWEEN RED WIRES
(BOILER TEMP BELOW 170F)

LIMIT CIRCUIT APPEARS OK -
RECYCLE BOILER A FEW TIMES AFTER
PLUGGING IN "CONTROL" PLUG

CHECK FOR CONTINUITY ACCROSS
OPERATING CONTROL CONTACTS

REPLACE SAFETY LIMIT

REPLACE OPERATING
CONTROL

ALL LIMITS OK.
BOILER SHOULD CYCLE PROPERLY ON
A CALL FOR HEAT OR HOT WATER

PUSH SAFETY LIMIT RESET
BUTTON* BUTTON CLICKS

(0 OHMS ON LOW

OHM SCALE)

CONTINUITY

CONTINUITY

CONTINUITY

NO CONTINUITY

( OHMS)

NO CONTINUITY

TESTING LIMIT CIRCUIT

(YOU MUST COMPLETE PAGE 16 FIRST)

NOTE: AFTER COMPLETEING LIMIT CIRCUIT TESTING, PLUG IN CONTROL PLUG AND RECYCLE
BOILER A FEW TIMES. IF BOILER A BOILER DOES NOT RECYCLE CONNECT A JUMPER TEMPORARILY
BETWEEN THE RED WIRES. IF BOILER STARTS REMOVE JUMPER AND TEMPORARILY JUMP EACH
SAFETY CONTROL UNTIL THE DEFECTIVE CONTROL IS LOCATED. NEVER LEAVE A SAFETY CONTROL
JUMPED.
* CHECK BOILER PUMP IF SAFETY LIMIT HAS TRIPPED.

CONTINUITY

CHECK FOR

CONTINUITY ACROSS

VENT (EXHAUST) TCO

YES

NO

NO OVERHEAT CONDITION
HAS OCCURRED

CHECK FOR CONTINUITY ACCROSS
SAFETY LIMIT CONTACTS

NO CONTINUITY

REPLACE VENT
(EXHAUST) TCO

NO
CONTINUITY