RESET BOILER BY SWITCHING POWER OFF FOR
15 SECONDS - WHEN "VALVE/FLAME" LITE LIGHTS
IS THERE 24 VAC BETWEEN ORANGE AND YEL-
LOW WIRES ON GAS VALVE AND/OR DOES GAS
VALVE CLICK?

TURN ON VALVES, FILL LP TANK ON LP UNIT
- IF REQ'D - RESET BOILER BY SWITCHING
POWER OFF FOR 15 SECONDS. RUN
THROUGH TWO TO THREE CYCLES

CHECK TCO AND INTAKE TCO FOR CONTINUITY

DOES BURNER IGNITE AND
APPEAR TO RUN PROPERLY?

NUISANCE LOCKOUT CAUSED FLASHING
LITE - CHECK COMBUSTION

CHECK IGNITER-
IGNITER OK?

CHECK FOR GAS FLOW
- IS METER MOVING?

REPLACE
IGNITER

REPLACE INTEGRATED BOILER CONTROL P/N 2400-224

INSTALL
CORRECT
ORIFICES

BOILER CYCLES THROUGH THREE CYCLES AFTER
RESETTING AND "VALVE/FLAME" LITE FLASHES

CHECK GAS AND AIR ORIFICE
FOR PROPER SIZE

REPLACE GAS VALVE

ARE GAS VALVES AND GAS METER TURNED ON.
IS THERE GAS IN LP TANK (LP UNITS).

YES

YES

YES

YES

YES

NO

NO

NO

INCORRECT

CORRECT

RED "VALVE/FLAME" LIGHT FLASHING

(YOU MUST COMPLETE PAGE 16 FIRST)

NO

NO

REPLACE

DEFECTIVE

TCO

CHECK

WIRES TO

GAS VALVE

CONTINUITY
(0 OHMS)

NO CONTINUITY
( OHMS)

REPLACE

INTEGRATED

BOILER

CONTROL P/

N 2400-224

CORRECT

WIRING

OK

FAULTY