9600 CB & HWG Service Manual

Page 19

NO CONTINUITY

( OHMS)

1. SWITCH OFF BOILER SWITCH
2. REMOVE BOTH TUBES FROM

STACK SWITCH AND DISCONNECT

ELECTRICAL WIRES
3. CHECK FOR CONTINUITY ACROSS
SWITCH TERMINALS

1. ATTACH TUBES DISCONNECTED

FROM STACK SWITCH TO U-TUBE
MANOMETER

2. SWITCH ON BOILER TO OPERATE

BLOWER

3. MANOMETER INDICATES 1.5" W.C.

OR GREATER

REPLACE STACK
SWITCH P/N 2400-110

RECONNECT STACK SWITCH
TUBES AND CHECK FOR
CONTINUITY BETWEEN STACK
SWITCH TERMINALS WITH
BLOWER OPERATING

CHECK FOR VENT OBSTRUCTIONS

CLEAR OBSTRUCTIONS &
RECONNECT TUBES & ELEC-
TRICAL WIRES TO STACK
SWITCH - START BOILER &
RUN THROUGH A FEW
CYCLES

STACK SWITCH OK

REPLACE STACK
SWITCH P/N 2400-110

CONTINUITY

(0 OHMS)

NO CONTINUITY

( OHMS)

CONTINUITY

(0 OHMS)

OBSTRUCTED

CLEAR

NO

YES

CHECK BLOWER

PAGE 20

NOTE: CHECK TUBES ON STACK SWITCH FOR PROPER CONNECTIONS
TUBE CONNECTION CLOSEST TO YOU SHOULD CONNECT TO BARBED TEE FITTING ABOVE AIR ORIFICE.

CHECKING STACK SWITCH

(YOU MUST COMPLETE PAGE 16 FIRST)