LAARS Mascot ll LMC - Install and Operating Manual User Manual

Page 14

Advertising
background image

LAARS Heating Systems

Page 12

Figure 10. Vent Dimensions, 2-Pipe System.

Massachusetts

In Massachusetts the following items are required

if the side-wall exhaust vent termination is less than

seven (7) feet above finished grade in the area of the

venting, including but not limited to decks and porches.

From Massachusetts Rules and regulations 248 CMR

5.08

1. Installation of Carbon Monoxide Detectors

At the time of installation of the side wall vented

gas fueled appliance, the installing plumber or

gasfitter shall observe that a hard-wired carbon

monoxide detector with an alarm battery back-up is

installed on the floor level where the gas appliance

is to be installed. In addition, the installing plumber

or gasfitter shall observe that a battery operated or

hard-wired carbon monoxide detector with an alarm

is installed on each additional level of the dwelling,

building or structure served by the side-wall

horizontally vented gas fueled equipment. It shall

be the responsibility of the property owner to secure

the services of qualified licensed professionals

for installation of hard-wired carbon monoxide

detectors.

a. In the event that the side-wall horizontally vented

gas fueled equipment is installed in a crawl space or

an attic, the hard-wired carbon monoxide with alarm

and battery back-up may be installed on the next

adjacent floor level.

b. In the event that the requirements of the

subdivision cannot be met at the time of completion

of installation, the owner shall have a period

of thirty (30) days to comply with the above

requirements, provided, however, that during said

thirty (30) day period, a battery operated carbon

monoxide detector with an alarm be installed.

2. Approved Carbon Monoxide Detectors

Each carbon monoxide detector shall comply with

NFPA 720 and be ANSI/UL 2034 listed and IAS

certified.

3. Signage

A metal or plastic identification plate shall be

permanently mounted to the exterior of the building

at a minimum height of eight (8) feet above grade

directly in line with the exhaust vent terminal for

horizontally vented gas fueled heating appliance

or equipment. The sign shall read, in print no less

than one-half (1/2) inch in size: "GAS VENT

DIRECTLY BELOW, KEEP CLEAR OF ALL

OBSTRUCTIONS".

4. Inspection

The state or local gas inspector of the side-wall

horizontally vented gas fueled appliance shall not

approve the installation unless, upon inspection, the

inspector observes carbon monoxide detectors and

signage installed in accordance with the provisions

of 248 CMR 5.08(2)(a) 1-4.

3.4 Common Vent Test

NOTE: This section does not describe a method for

common venting Mascot II units. It describes what must

be done when a unit is removed from a common vent

system. Mascot II units require special vent systems and

fans for common vent. Contact the factory if you have

questions about common venting Mascot II units.

When an existing boiler is removed from a

common venting system, the common venting system is

likely to be too large for proper venting of the appliances

remaining connected to it.

At the time of removal of an existing boiler, the

following steps shall be followed with each appliance

remaining connected to the common venting system

placed in operation, while the other appliances

remaining connected to the common venting system are

not in operation.

1. Seal any unused openings in the common venting

system.

2. Visually inspect the venting system for proper

size and horizontal pitch and determine there is no

blockage or restriction, leakage, corrosion and other

deficiencies which could cause an unsafe condition.

3. Insofar as it is practical, close all building doors and

windows and all doors between the space in which

the appliances remaining connected to the common

venting system are located and other spaces of the

building. Turn on clothes dryers and any appliance

not connected to the common venting system.

Turn on any exhaust fans, such as range hoods and

bathroom exhausts, so they will operate at maximum

speed. Do not operate a summer exhaust fan. Close

fireplace dampers.

4. Place in operation the appliance being inspected.

Optional concentric vent kit sold separately.

Advertising