Mascot II Boilers and Water Heaters

Page 23

SECTION 7.

Electrical Connections

WARNING

The appliance must be electrically grounded in

accordance with the requirements of the authority having

jurisdiction or, in the absence of such requirements, with

the latest edition of the National Electrical Code, ANSI/

NFPA 70, in the U.S. and with latest edition of CSA

C22.1 Canadian Electrical Code, Part 1, in Canada. Do

not rely on the gas or water piping to ground the metal

parts of the boiler. Plastic pipe or dielectric unions may

isolate the boiler electrically. Service and maintenance

personnel, who work on or around the boiler, may be

standing on wet floors and could be electrocuted by an

ungrounded boiler. Electrocution can result in severe

injury or death.

Single pole switches, including those of safety

controls and protective devices must not be wired in a

grounded line.

All electrical connections are made on the terminal

blocks that are located inside the control panel.

NOTE: All internal electrical components have been

prewired. No attempt should be made to connect

electrical wires to any other location except the terminal

blocks.

Wiring connections are shown in

Figures 21-22.

Important Note: DO NOT MAKE/BREAK MASCOT II

LINE VOLTAGE TO SIGNAL CALL FOR HEAT. A “call

for heat / end call for heat” MUST be connected to the

field interlock terminals. Some Mascot II components

are designed to have constant voltage during normal

operation. If the Mascot II's supply voltage is toggled

as a call for heat signal, premature failure of these

components may result.
If using remote 4-20mA control, Mascot II does not

recognize 4mA as a signal to shut off. If the call for heat

is not connected between the field interlock terminals,

Mascot II will remain in low fire when it sees 4mA as a

modulating signal.

Caution

Mascot II supply voltage must not be disengaged,

except for service or isolation, or unless otherwise

instructed by procedures outlined in this manual. To

signal a call for heat, use the 24V field-interlock, as

shown in the wiring diagram(s).

7.1 Main Power

Plug power cord into a non-switched 115V

electrical outlet with 15A circuit protection. FLA is

2A. There is an internal 10A breaker to protect internal

system components.

7.2 Pump Connections

Mascot II energizes the integral boiler pump (and

three-way valve if central heat) upon a call for heat.

Once the call for heat is satisfied the pump will remain

on for the defined pump overrun time.

NOTE: System pump contacts are dry contacts.

Appropriate voltage must be supplied to the System

pump for proper operation.

System pump connections are located in the

control panel (

see Figure 20

). The system pump contacts

are rated for 120Vac, 7.4 amps. To use the contacts,

power must be supplied on one terminal with the other

terminal wired to the pump or a relay controlling the

pump.

7.3 24Vac Transformer with Circuit Breaker

24Vac is supplied by a transformer mounted behind

the upper door. All 24Vac power is supplied through a

2A circuit breaker located behind middle door.

7.4 Central Heat - Call for Heat

Connect the Call for Heat to terminals #1 and #2

(connections labeled "T-T or interlock").

7.5 Outdoor Air Temperature Sensor

Connect the outdoor air temperature sensor

to connections labeled "Outdoor temp sensor." The

outdoor air temperature sensor is used for warm weather

shutdown and outdoor reset.

7.6 Domestic Hot Water Connection

For LMH and indirect water heater, connect

aquastat for remote sensor to terminals 7 & 8 (see

Figures 20 and 22

).

7.7 System Sensor

(lead lag/cascading operation only)

Connect the system sensor to connections labeled

"system sensor."

7.8 External Control Connections

Connect 4-20mA signals from external controls

or building automation systems. When making the

connections, follow the polarity designations shown on

the label.

7.9 Lead Lag / Cascading Wiring

Connections

Connect each boiler in the cascade system together

by daisy chaining each control from Modbus port 1

(MB1) of the first boiler to the second and so on. This

can be done using 22awg or thicker shielded twisted pair

wire with drain. Two twisted pairs or three conductors

are needed.

a. To daisy-chain the boilers connect a wire from

Modbus port 1 (MB1) terminal A of the first boiler

to Modbus port 1 (MB1) terminal A of the second

boiler.