Mascot II Boilers and Water Heaters

Page 13

Follow the lighting instructions. Adjust thermostat

so the appliance will operate continuously.

5. Test for spillage at the draft hood relief opening

after 5 minutes of main burner operation. Use

the flame of a match or candle, or smoke from a

cigarette, cigar or pipe.

6. After it has been determined that each appliance

remaining connected to the common venting system

properly vents when tested as outlined above, return

doors, windows, exhaust fans, fireplace dampers and

any other gas burning appliance to their previous

conditions of use.

7. Any improper operation of the common venting

system should be corrected so that the installation

conforms to the National Fuel Gas Code, ANSI

Z223.1/NFPA 54 and/or CSA B149.1, Installation

Codes. When resizing any portion of the common

venting system, the common venting system

should be resized to approach the minimum size

as determined using the appropriate tables and

guidelines in the National Fuel Gas Code, ANSI

Z223.1 NFPA 54 and/or CSA B149.1, Installation

Codes.