LAARS Mascot ll LMC - Install and Operating Manual User Manual

Page 37

Advertising
background image

Mascot II Boilers and Water Heaters

Page 35

complete installation of this kit. The installation is

not proper and complete until the operation of the

converted appliance is checked as specified in the

manufacturer's instruction supplied with the kit.

AVERTISSEMENT

Ce conversion doit être installé par un organisme de

service conformément aux instructions du fabricant

et tous les codes et les exigences de l'autorité

compétente. Si les informations contenues dans ces

instructions n'est pas suivi à la lettre, un incendie,

une explosion ou de la production de monoxyde

de carbone mais résultat causant des dommages

matériels, des blessures ou des pertes de vie. Le

service est responsable pour la bonne et complète

l'installation de ce kit. L'installation n'est pas correcte

et complète jusqu'à ce que le fonctionnement de

l'appareil converti est vérifiée comme spécifié dans le

manuel d'instruction fourni avec le kit.

Conversion to/from LP Gas Instructions:

Kit #

R2075500

1. Remove the front covers.
2. Follow the shutdown procedure as indicated in the

Lighting/Shutdown Instructions shown on inside

front cover or side of appliance.

3. Turn off the gas supply to the boiler.

Arrêtez l’approvisionnement en gaz à chaudière.

4. Turn off the main electrical supply to the boiler.

Arrêtez l’alimentation électrique principale à

chaudière.

5. Confirm that the actual gas supply is propane

(confirm natural gas if converting to natural gas).

6. Install correct “Propane Gas” sticker over the

“Natural Gas” sticker (or vice versa).

7. Fill out Gas Conversion Sticker completely and

install adjacent to the rating plate sticker (behind

the door panel).

8. Remove Gas Pipe from the outlet of the Gas Valve.

(Note: You do not have to remove the gas valve

from the unit).

9. Insert (or remove) Propane Gas Orifice

(Part# 12H6010) from valve outlet.

10. Ensure the gas O-Ring is in the Gas Pipe Flange

Groove.

11. Re-Install Gas pipe.
12. Purge Old gas from the line.
13. Confirm Gas supply is on.
14. Connect power supply.
15. Start boiler per lighting procedure shown on inside

front cover or side of appliance.

16. Check for Gas Leaks at gas valve/pipe.
17. With a combustion analyzer, check CO2 and CO

levels at both maximum and minimum input.

SECTION 12.

Trouble Shooting

12.1 Sequence of Operation

Mascot II is a cold start appliance that should

start only on a call for heat from a tank aquastat, room

thermostat, zone valve end switch or other space

temperature control device (flow switch for DHW).

1. Upon a call for heat: (a) the internal pump and

system pump will start; (b) the blower will begin a

short pre-purge.

2. Following the prepurge cycle the direct spark

ignition will spark and will begin a 4 second

trial for ignition. The unit is allowed one or three

ignition retries.

3. The gas valve will then be energized and a reduced

rate ignition will occur. The unit will remain in a

reduced rate start-up period for several seconds.

4. After the reduced rate start time is over, the

unit will be in normal operation. Firing rate

will modulate based on the heating load via the

temperature controller settings and readings.

5. When the call for heat is complete, or the unit

reaches its setpoint temperature, the gas valve will

close, and the fan will continue to run for its post-

purge. If a pump delay time is used, the pump will

continue to run for the specified amount of time

(adjustable from 0.1 to 10 minutes).

12.2 Short Cycling

Because Mascot II is a modulating boiler, and its

input will decrease when there is a reduction in heating

load, short cycling is greatly reduced. If the heating

load drops below the minimum input of the boiler for

an extended period, the boiler will have a tendency to

short cycle. This can be a symptom of improper control

or piping layout. When in DHW mode under low load

conditions, the boiler will normally cycle more often,

but should not cycle frequently during call for central

heating.

12.3 Error Codes -

See

Table 14

.

18. Adjust as needed to achieve proper levels. Refer

to sections 10.2.2 and 10.2.3 of this manual for

the proper adjusting procedures.

19. Re-Install front covers.