LAARS Heating Systems

Page 36

CODE# PROBLEM

PROBABLE CAUSE

SOLUTION

COMMON LOCKOUT CODES

27 Internal error

Flame rod to ground

Check wiring / probe grounded, dirty probe

47 Flame rod to ground leakage

Faulty flame detector

Clean or replace flame detector

49 24VAC voltage low/high

Faulty transformer

Check/correct supply line voltage; replace faulty

transformer

52 Motor tachometer fault

Faulty fan / fan wiring

Check fan harness wiring for continuity; replace faulty

fan circuit

53 AC inputs phase reversed

Reverse 24V hot/neutral - use common ground

61 Anti short cycle

Call for heat will be held

Change ASC timer setting

until timer resets

62 Fan speed not proved

Dirty / defective fan

Clean or replace fan; check wiring

63 LCI off

Safety chain interrupt

Check flow switch, aux high limit, LWCO, gas

pressure switches, condensate level and correct

problem

69 Outlet high limit

High limit tripped

Determine cause: low/no flow, valves closed, settings

and correct

79 Outlet high limit

80 DHW high limit

High limit reached

Check pump, time delay, valves closed, etc. and

81 Delta T inlet/outlet limit

correct overtemp

82 Stack limit

High limit reached

Could be caused by high ambient temperature, or

high return water temperature

88 Outlet T-rise limit
90 Heat exchanger high limit

High limit reached

Diagnose / repair cause of high temperature

91 Inlet sensor fault
92 Outlet sensor fault

93 DHW sensor fault

Faulty sensor or wiring

Check wiring / replace sensor; condition can be

95 Stack sensor fault

caused by short

96 OAT temperature sensor fault

Faulty outdoor air

Check wiring and sensor for short; replace sensor

temperature sensor

is open or shorted

105 Flame detected

Flame exists at burner

Clean burner of soot or other debris

that could

out of sequence

when it should not be

maintain flame

106 Flame lost in MFEP

Unstable flame during

107 Flame lost early in Run

lighting / flame proving

Check venting, gas supply pressure, burner, fan, etc.

108 Flame lost in Run

sequence

109 Ignition failed

Problem with ignitor, or

Check / replace ignitor, wiring; check for shorting

other ignition-related device in ignitor cable

113 Flame circuit timeout

Flame not established

Check all combustion components; purge gas;

within expected time limit

check ignition source

122 Lightoff rate proving failed

123 Purge rate proving failed

128 Fan speed failed / prepurge

Fan did not reach

Check fan wiring; replace fan

129 Fan speed failed / preignition

expected RPM

130 Fan speed failed / ignition
131 Fan movement detected

Fan should not be moving

Check for common venting problems or otherwise

during standby

when not powered

forced air

132 Fan speed failed during run

Fan lost or gained speed

Fan overheating or otherwise failing; check cable;

during run sequence away

replace fan

from control spec

137 ILK failed to close

No power at interlock ILK

Check J5 pin 1 for power - if no power, confirm

safeties are closed

49 Maximum cycle count

Control operates correctly,

continued next page >