Out of production – LAARS Mighty Max HH (Sizes 320M - 400M) - Installation, Operation and Maintenance Instructions User Manual

Page 20

Advertising
background image

Page 20

LAARS Heating Systems

Immediately call your gas supplier from a

neighbor's phone. Follow the gas supplier's

instructions.

If you don't smell gas, go to the next step.

7.

Turn on manual gas valves.

8.

Rest all safety devices (manual resets on high

limit, low water cutoff, etc.).

9.

Replace control access panel.

10. Turn on all electric power to the boiler.

11. Set thermostat to desired setting.

12. If the boiler will not operate, follow the

instructions to turn off gas to boiler and call your

service technician or gas supplier.

a.

Turn off main electrical switch.

b.

Close all manual gas valves.

3.4.1 Setting Temperature Controls
The temperature control differential is factory

set at 15°F. This setting can be adjusted from 1 to

30°F to suit your application. Adjustment is made by

taking the cover off the temperature controller and

turning the potentiometer marked “DIFF”, which is

located just below and to the left of the controller’s

setpoint dial.

To set the temperature and high-limit controls:

a.

Set the temperature controller at the system

design temperature.

b.

For boilers with the temperature controller bulb

at the boiler inlet, set the high-limit 40°F to 50°F

above temperature controller setting.

c.

For boilers with the temperature controller bulb

at the boiler outlet, set the high-limit 15°F to

25°F above temperature controller setting.

3.5 To Shut Down System

To shut down the boiler, turn off all manual gas

valves and electrical disconnect switch.

NOTE: There is a filter which needs to be cleaned
prior to setting pressures. See Section 4.4.2 “Filter
Service” before proceeding.

3.6 Venturi Adjustment - Natural Gas

Verifying proper operation of the combustion

flow system has two aspects - air flow and gas flow.

Air flow is checked by measuring pressures at service

taps on the venturi. Gas flow is checked by evaluating

venturi pressures and the regulator offset pressure.

In a venturi flow system the difference between

various pressures is far more important than their

“gauge” value relative to the room. The gas pressure

offset and the gas orifice pressure differential are

especially important concepts. The following section

describes this setup procedure.

3.6.1 Pressure Measurement Ports -

Natural Gas

Air flow enters the venturi through the filter box

and blower assembly. It is pushed through a

converging section and into the throat, where pressure

is reduced substantially. Gas flow is pulled into the

throat through an orifice. The orifice is located

between the throat and the regulator. Air and gas are

combined in the throat and mix thoroughly as they

proceed through the venturi tailpipe to the burner.

Service taps are provided at three places. One is

located on the chamber with the gas connection, this

tap is called the gas plenum tap. The other is located

above the gas plenum tap, this port is called the

venturi inlet tap. The third tap, gas orifice tap, is

located on the red orifice holder directly before the gas

connects to the venturi. These taps have service plugs

in them. Do not remove any of the plastic fittings or

plastic tubing. To evaluate system operation requires

accurate measurement at these taps. An inclined

manometer with a zero to 6 inches water column range

is ideal. Other instruments may be used, but the

“positive/negative” nature of the readings must be

well understood. Gas pressure offset measurements are

at very low levels (0.4" WC), the instrumentation must

be capable of determining it accurately (see Figure 15,

16 and 17).

3.6.2 Adjustment Procedure - Natural Gas
Note that an equalizer tube is connected from a

port on the side of the venturi inlet to the port of the

regulator. This is a very important component which

allows the regulator to track air pressure even when

abnormal conditions occur, such as blockage of the

combustion air. Before firing, confirm that this tube

Overall

Operation

Figure 14. Typical Venturi System.

Air

Equalizer

Tube

Negative

Pressure Regulator

Gas

Gas

Orifice

Air/Gas
Mixture

OUT OF

PRODUCTION

Advertising