Mighty Max Hydronic Boiler

Page 7

Notes: 1. These numbers are based on 1/2 inch (13mm) water column pressure drop.

2. Check supply pressure and local code requirements before proceeding with work.
3. Pipe fittings must be considered when determining gas pipe sizing.

Table 3. Natural Gas and Propane, Pipe Size Requirements.

Distance from Gas Meter or Last Stage Regulator

0-100 feet

100-200 feet

200-300 feet

0-30m

30-60m

60-90m

Natural

Propane

Natural

Propane

Natural

Propane

Size

in.

mm

in.

mm

in.

mm

in.

mm

in.

mm

in.

mm

320M

1.25

32

1.25

32

1.50

38

1.25

32

1.50

38

1.50

38

400M

1.25

32

1.25

32

1.50

38

1.25

32

2.00

51

1.50

38

3.

The figures in Table 3 should be used to size the

gas piping from the gas meter to the boiler.

Check local codes for BTU/h capacity required.

4.

Install a sediment trap (drip leg) ahead of the gas

controls (see Figure 4). Fit the trap with a

threaded cap which can be removed for cleaning.

5.

When required by code, install a second manual

gas shutoff valve. Do not remove manual shutoff

valve supplied with the boiler.

6.

Disconnect the boiler and its individual shutoff

valve from the gas supply piping system during

pressure testing of the system at pressures higher

than 1/2 psi (3.5 kPa). Isolate the boiler from the

gas supply piping system by closing its

individual manual gas shutoff valve during any

pressure testing of the gas supply piping system

at test pressures equal to or less than 1/2 psi

(3.5 kPa).

7.

Gas supply pressures to the boiler are listed in

Table 4.

Supply Pressure

Water Column

Natural Gas

Propane Gas

in.

mm

in.

mm

Minimum

5

127

9

229

Maximum

9

229

14

356

Table 4. Gas Supply Pressure Requirements.

NOTE: The boiler and all other gas appliances
sharing the boiler gas supply line must be firing at
maximum capacity to properly measure the inlet
supply pressure. Low gas pressure could be an
indication of an undersize gas meter and/or
obstructed gas supply line.

8.

Do not exceed the maximum inlet gas pressures

specified. Excessive pressure will result in

damage to the heater's gas controls. The

minimum pressures specified are for gas input

adjustment.

9.

The correct differential gas pressure is stamped

on the rating plate. The regulator is preset at the

factory, but may need adjustment for altitude per

Section 3.

10. Before operating the heater, test the complete gas

supply system and all connections for leaks using

a soap solution.

CAUTION

Since some leak test solutions (including soap and
water) may cause corrosion or stress cracking,
rinse the piping with water after testing.

ATTENTION

Comme certaines solutions qui testent les fuites (y
compris le savon et l’eau) peuvent causer de la
corrosion ou des fissures sous stress, rincez les
tuyaux avec de l’eau après les tests.

2.7 Water System Requirements

2.7.1 Flow Requirements
The Model HH boilers must have continuous

flow through the heat exchanger when firing for

proper operation. The system pump must be capable

of developing sufficient pressure to overcome the

resistance of the boiler plus the entire circulating

system at the designated flow (see Table 5). The

temperature rise across the boiler should never exceed

20°F (11°C). Minimum inlet water temperature is

120°F (49°C).