Out of production – LAARS Mighty Max HH (Sizes 320M - 400M) - Installation, Operation and Maintenance Instructions User Manual

Page 26

Advertising
background image

Page 26

LAARS Heating Systems

2.

The “IND” terminal of the ignition control is

energized for a 15 second pre-ignition purge

period during which the combustion blower

purges the combustion chamber.

3.

After the purge period there is a 20 to 35 second

igniter heat up period. The glow of the igniter

can be seen through the boiler sight glass.

4.

Then there is a seven second trial for ignition.

During this time the gas valves are energized and

the main burner ignites. The gas valves will

remain energized throughout the call for heat as

long as the ignition control igniter senses a stable

flame.

5.

After the call for heat is satisfied the ignition

control closes the gas valves and operates the

blower for a thirty (30) second post purge cycle.

This clears the combustion chamber of

combustion products.

The ignition is attempted three times. If ignition

is not successful, the control shuts down and “locks

out”. It remains in the lockout condition until the

boiler is turned off then back on or 120 Vac power to

the boiler is interrupted.

5.2 Venturi and Gas Pressure Regulator

System

5.2.1 Field Checkout
See Section 3.2 “Venturi and Gas Pressure

Regulator System” for proper setup procedure.

5.3 Electrical Components

This section describes guidelines for checking

the operation of electrical components installed on the

boiler. Refer to the wiring diagram for correct

connection locations.

5.3.1 General Troubleshooting
This section describes guidelines for checking

the electrical components of the boiler. Experience has

shown that most complaints about boilers failing to

fire have nothing to do with the boiler itself. Usually,

one of the protective switches in the boiler system has

shut down operation.

Any of the following can prevent proper

operation. Check these items first:

1.

Be sure the boiler has been properly installed

(see Section 2).

2.

Make sure the pump is not airlocked, clogged or

otherwise inoperative.

3.

Make sure the gas valve is on and there is

sufficient gas pressure in the line. All external

gas valves must be open.

4.

Verify that the electrical circuit serving the boiler

is ON.

5.

Make sure the toggle switch on the right side of

the boiler is ON.

6.

Check the fuse inside the black, twist-lock fuse

holder. If it is burned, replace it with a 2-amp

fuse (part no. E0084400).

7.

With the power off inspect all electrical

connections and wiring. Finding a loose

connection or charred wire can save a lot of time

and money.

8.

Make sure the temperature controller is set high

enough to call for heat.

9.

Make sure none of the manual reset controls, i.e.,

low water cutoff, high limit, etc., have tripped.

Reset any tripped switches.
If the pump is circulating water and the

foregoing items check out okay, the trouble may be in

the boiler control system.

CAUTION

Disconnect power to the boiler before removing or
replacing any component or wire connection. If the
power is not disconnected, “jumping” the gas valve
or accidentally grounding the wire harness or
component terminals to the boiler frame or jacket
could cause the ignition control fuse to blow.

ATTENTION

Débranchez la chaudière avant d’enlever ou de
remplacer tout élément ou branchement de fil. Si la
chaudière est branchée, « connecter » la valve de
gaz ou mettre accidentellement à la terre le
faisceau de fils ou des terminaux au corps ou à la
gaine de la chaudière peut faire sauter le plomb
(ou disjoncteur) de la commande d’allumage.

5.3.2 Electrical Troubleshooting
Troubleshooting procedures should only be

performed by professional service technicians

qualified in heater maintenance.

Some electrical components are wired in parallel,

so it is necessary to troubleshoot in the order that they

appear on the wiring diagram or the troubleshooting

flow chart (see Figure 20).

NOTE: When testing the safeties between “MV1” of
the ignition control and the gas valve(s) there is only a
seven (7) second trial for ignition period during which
there is power to “MV1”.

The following steps should be used when

troubleshooting the boiler:

1.

Remove the lower front panel (see Figure 21).

2.

Turn the manual gas valve on the heater off.

3.

If the heater has locked out turn the toggle switch

off for 5 seconds then back on to reset the heater.

OUT OF

PRODUCTION

Advertising