Out of production – LAARS Mighty Max HH (Sizes 320M - 400M) - Installation, Operation and Maintenance Instructions User Manual

Page 25

Advertising
background image

Mighty Max Hydronic Boiler

Page 25

4.

Inspect the filter for discoloration due to

contamination or any other forms of debris. If

contamination or debris exists, wash the filter in

a soap/water solution then rinse with water only.

It is important that the filter be dry before

placing it back in the filter housing.

CAUTION

The filter has arrows which indicate the direction of
the air flow. Failure to install the filter correctly may
cause blower failure and dangerous operation.

ATTENTION

Le filtre a des flèches qui indiquent la direction de
l’air. Si le filtre n’est pas installé correctement, le
souffleur peut ne pas fonctionner, ce qui serait
dangereux.

The filter must be inspected for contamination

one week after start-up. Depending upon the severity

of contamination, a suitable cleaning schedule may be

developed. The factory recommends cleaning the filter

at least once every 30 days. In high contamination

areas, such as construction sites, factories, etc., the

filter may need to be cleaned daily. Failure to do so

could result in lower heat output and potential unsafe

operation.

SECTION 5.
Troubleshooting

5.1 Sequence of Operation

To troubleshoot the heater properly you must

first understand the sequence of operation of the

heater:

1.

Upon a call for heat a 24 Vac signal is sent

through fusible links and high limit(s) to the

ignition control “TH” terminal.

4.2.2b. Cleaning the Heat Exchanger -

Internal

1.

Remove the inlet/outlet header of the heat

exchanger.

2.

Remove the return cover of the heat exchanger.

3.

Clean the internal surface. (Laars offers a tube

cleaning kit part no. R00100000.)

4.

Reassemble in the reverse order.

4.3 Gas and Electric Controls

The gas and electric controls on the heaters are

designed for both dependable operation and long life.

Safe operation of the heater depends on their proper

functioning. A professional service technician should

check the following basic items every year, and

replace when necessary.

NOTE: the warranty does not cover damage caused
by lack of required maintenance or improper
operating practices.

1.

Water temperature controls.

2.

Ignition control system.

3.

Automatic electric gas valve(s).

4.

Flow sensing safety device (when used).

5.

Low water cutoffs, including flushing or float

types. (Every six months)
Other maintenance requirements include:

1.

Periodic cleaning of filters, when supplied.

2.

Lubrication of moving parts (when applicable),

with the correct type and amount of lubricant.

3.

Periodic examination of the venting system.

4.

Periodic cleaning of vent terminal screens, where

applicable.

5.

Cleaning flue gas passageways.

4.4 Filter

4.4.1 Filter Function
A filter has been designed into the operation of

this Mighty Max boiler. Its function is to filter the

combustion air before it is delivered to the burner

system. The filter is manufactured out of a

polyurethane foam and may be cleaned with a mild

soap and water solution. Clean the filter only after the

filter has been removed from the filter housing (see

Figure 19).

4.4.2 Filter Service
(The filter does not need cleaning if this is a first

time heater start-up).
1.

Turn the heater off using the toggle switch.

2.

Remove the door panel and bonnet from the

jacket.

3.

Remove the screws on the filter housing to

expose the filter as shown in Figure 19.

Figure 19. Filter Exposed for Cleaning.

FILTER

ARROW

OUT OF

PRODUCTION