Programming

7-6

Mapping to Zone Events

Eleven types of events can occur in zones. For each event type, you can activate up to 8 output groups or output
group templates, specifying a pattern for each. The following is a list of all event types:

Note: Abbreviations in the parenthesizes are the characters that are displayed in programming (see

Figure 7-4).

Manual Pull Alarm (MP)

Water Flow Alarm (WF)

Detector Alarm (DE). This applies to heat or smoke detectors.

Aux 1 and Aux 2 Alarm (A1 or A2). User-specified alarm types.

Pre-alarm (PR)

Supervisory (SU)

Trouble (TR)

Status Point (SP)

CO Alarm (CO)

CO Supervisory (SCO)

To map zone events to outputs:

1.

From the Installer Main Menu, select 7 for Program Menu.

2.

From the Program Menu, select 2 for Zone.

3.

From the next menu, select 1 for Edit Zone.

4.

Enter the zone number you wish to edit.

5.

From the next menu, select 3 for Zone Outputs.

6.

A screen similar to the one shown in Figure 7-4 will display. Select the event type you want to program

using the

or

key and press ENTER.

7.

Press the

or

key to toggle the group letter to either G = Group or T = output group template depend-

ing on want you need for this zone. Press ENTER.

8.

Select options for each event that could occur in this zone. Figure 7-4 is a complete example of how you
might map a zone.

Figure 7-4 Selecting Output Groups/templates and Cadence Patterns for a Zone Event

Zone Mapping Example

Suppose you want to program Zone 1 so that:

Any alarm (detector, CO, water flow or manual pull) would activate Output Group 1 using the ANSI
cadence pattern.

Manual pull alarm would activate Output Group 3 using constant output.

Indicates type of event (in
this case, Manual Pull alarm).
See Section

7.5

for choices.

Indicates output group 1, cadence
pattern 00 has been selected. 00 is
a constant output cadence.

“T” Indicates output group
template 1. See Section 7.4.5
for
more information on output group
templates.