System Operation

8-16

8.7.1

Single Interlock Zone Releasing

A single interlock zone utilizes a minimum of two addressable detectors and a designated manual release switch.

Conditions Required for an Pre-Alarm Output Activation

If any single addressable detector is activated, the “Pre-Alarm” output will activate. This alerts the user that the
initial stages required for a release condition are present. (Also refer to Table 8-3.)

Conditions required for an General Alarm and Release Output Activation

If two or more addressable detectors, or a manual release switch activate, the “Alarm” and the “Release” outputs
will activate and the “Pre-Alarm” output will deactivate. (Also refer to Table 8-3.)

Important!

Only addressable detectors can be used. No conventional detectors can be used.

Each Single Interlock Zone input requires at least one manual release switch.

Table 8-3: Single Interlock Zone Operation

Inputs

Output Results

1st Addressable Detector

x

x

x

x

2nd Addressable Detector

x

x

x

x

Manual Release Station

x

x

x

x

Nor

m

al

Pre-Alarm

Pre-Alarm

Rele

ase and

Gen

e

ra

l Alarm

Rele

ase and

Gen

e

ra

l Alarm

Rele

ase and

Gen

e

ra

l Alarm

Rele

ase and

Gen

e

ra

l Alarm

Rele

ase and

Gen

e

ra

l Alarm