4 time options, 1 water flow delay, 2 alarm verification time – SilentKnight 5820XL User Manual

Page 136: 1 water flow delay 7.6.4.2 alarm verification time, Section 7.6.4.1, Section 7.6.4.2

Advertising
background image

LS10061-001SK-E

Programming

7-28

required for your application.

Figure 7-16 Special Cadence Patterns for Fire Drill and Auxiliary Alarm Events

7.6.4

Time Options

Through this programming option you can set the water flow delay time, Alarm Verification, low AC report
delay, AMPM/Military time and AC Frequency.

To change time options, follow these steps.

1.

Enter the installer code. The panel will automatically go to the main menu.

2.

Select 7 for Program Menu.

3.

Select 5 for System Options.

4.

Select 5 for Time Options.

7.6.4.1

Water Flow Delay

You can program a delay of 0-90 seconds (zero means no delay) to be used in conjunction with a water flow
switch. The delay is system-wide. All water flow switches on the system will use the same delay period.

To access the screen for programming water flow delay, follow these steps:

1.

Enter the installer code. The panel will automatically go to the main menu.

2.

Select 7 for Program Menu.

3.

Select 5 for System Options.

4.

Select 5 for Time Options.

A screen similar to the one shown in Figure 7-17 will display.

Figure 7-17 Water Flow Delay Programming Screen

5.

Enter the number of seconds (0 to 90) to delay an a water flow switch alarm, then press ENTER.

7.6.4.2

Alarm Verification Time

You can set the alarm verification time from 1 to 250 seconds (default is 60 seconds).

To set the alarm verification:

6.

Enter the desired number of seconds for the alarm verification time.

7.

Press the right arrow

or

ENTER to make your selection and move to the next programming option.

Delay in seconds
before waterflow
alarm occurs.
(00 - 90)