LS10061-001SK-E

Programming Overview

6-2

6.2.1

Input Points

JumpStart will determine the number and type of input points (detectors or contact monitor modules) on each
SLC loop. JumpStart assigns the correct detector type (heat, ionization or photoelectric), so the installer does not
need to edit the device type for detectors. Any contact monitor modules on the system will be assigned type
“Manual Pull.” The installer will need to manually change the switch type if manual pull is not correct.

JumpStart creates one zone (Zone 1) and assigns all input points to Zone 1. Zone 1 is mapped to Output Group 1.
If the system has an EVS-50W, EVS-INT50W, EVS-100W or EVS-125W Amplifier, then Output Group 2 will
also be created and all input points will be mapped to both Group 1 and Group 2. After JumpStart completes, you
can re-map to configure a multiple zone/output group system (see Section 7.3.1.3). For a general explanation of
mapping see Section 6.3.

6.2.2

Output Points

The 5820XL JumpStart creates three output groups. The 5820XL-EVS with amplifiers will create four output
groups. The output circuits are assigned as follows:

Circuits 1-6:
Configured as Notification and assigned to Group 1. JumpStart automatically programs Zone 1 to activate Group
1 using constant on output when an alarm condition occurs.

Circuit 7 (Relay 1):
Assigned to Group 249. JumpStart automatically programs Zone 1 to activate Group 249 using constant on
output when a supervisory condition occurs.

Circuit 8 (Relay 2):
Assigned to Group 250. JumpStart automatically programs Zone 1 to activate Group 250 using constant on
output when an alarm occurs.

Amplifier Circuits:
Assigned to Group 2. JumpStart automatically programs Zone 1 to activate Group 2.

Addressable output points (Relay modules, NAC Modules, Sounder Bases, Relay Bases):
All addressable relay devices will be configured as “Output Pt” (general purpose output point) and assigned to
Group 1.

Note: Relay output is constant even if the zone activating the relay is programmed with an output pattern.

6.2.3

Running JumpStart AutoProgramming

Run JumpStart immediately after you have addressed and connected all input devices (detectors, pull stations,
and etc.) and output devices (notification appliances, relays, etc.).

Note: If you need to install a few devices after you have run JumpStart, you can install them manually. Follow

instructions in Section 7 for configuration.

To run JumpStart, follow these steps:

1.

Select 7 for Program Menu. Enter the Access Code

2.

Select 6 for JumpStart AutoProgramming.

3.

The message “WARNING WILL DELETE all system options” displays on the LCD. Select Yes to continue.
A series of messages displays for the next several seconds. JumpStart scans the SLC loops for devices. This
can take several minutes, depending on the number of devices attached.

4.

When the message, “SLC FAMILY” message appears, select SK or SD; depending on the type of SLC
devices the panel is using, and press ENTER to accept.

5.

When the message “Configuring System Done” displays, press any key to continue.