Model 5820XL / 5820XL-EVS Installation Manual

LS10061-001SK-E

3-13

SLC Device Hardware Installation

Perform these steps before running JumpStart.

Connect device bases to the loop.

SK 5.5
SD 5.7

Set device addresses.

SK 5.6
SD 5.8

Physically connect detectors to their bases. Connect relay and contact monitor modules.

5.4 & see device

install instructions

JumpStart AutoProgramming

JumpStart is for initial system programming. JumpStart automatically selects some options for SLC devices.
See “Input Point (SLC Device) Configuration” section of this chart for other options.

JumpStart makes selections for the following options. You can customize options, if necessary.

6.2 & 7.7

Device type (detector or switch) configured by JumpStart.

To change, see 7.7

Program type of detector (heat, photoelectric, or ionization) selected by JumpStart.

To change, see 7.7

System Software Configuration

Select low AC hours report time (3 hours by default).

7.6.4.2

Select Auto Test Time (2:00 AM by default).

7.6.2

Enable/disable automatic DST adjustment feature (enabled by default).

7.6.6.1

Change clock display format (12-hour with AM/PM by default).

7.6.4.4

Set up reporting accounts.

7.6.1

Select options for phone lines.

7.6.2

Select system-wide response to trouble conditions, if desired.

7.6.3

Select system-wide cadence patterns for special conditions (fire drill, Aux1 and Aux2
alarms) if desired.

7.6.3.2

Customize banner message (message that displays on LCD in normal mode) if desired.

7.6.7

Input Point (SLC Device) Configuration

JumpStart automatically selects some options for SLC devices (see “JumpStart” section of this chart). You can change options
selected by JumpStart, if necessary and further customize input point options.

Select device family (SK or SD). Only one device family can be used per control panel.

7.6.8

Program type of switch (manual pull, fire drill, and so on), if necessary. (JumpStart assigns
all switches as Manual Pull type.)

7.5

If the installation includes duct detectors, program detector type. (JumpStart does not
distinguish duct detectors from ordinary smoke detectors.)

7.5

Assign a name (or description) to the point.

7.5.5

Assign input points to zones, if necessary. (JumpStart assigns all input points to Zone 1.)

7.5

Zone Configuration

Add the zone to the system if it does not already exist. (Zone 1 created by JumpStart.)

7.3.2

Program a name (or description) for the zone.

7.3.1.1

Select alarm delay options (detection characteristics) for zone.

7.3.1.2

Select heat detector trip temperature and/or smoke sensitivity level for photoelectric smoke
detectors. (JumpStart selects 150°F for heat detectors and Low sensitivity for smoke
detectors.)

7.3.1.2

Task

See Sec.

(for more info.)