In Connection diagram 2, attenuator-free broadcast can automatically be made using the digital
announcement machine, etc. when the attenuator-free broadcast switch is shorted. Determine broadcasting
lines by writing into the Integrated Control Panel EP-0510.

Notes

• In this connection example, because power (24 VDC) is always supplied from the battery built in the

emergency power supply panel for power-failure general/attenuator-free broadcasts to the digital announcer,
etc. (even when the attenuator-free broadcast switch is not shorted), the battery is drained quicker than in
the example of Connection diagram 1. Use the battery having a sufficient current capacity.

• The power-failure broadcast function is operated even when the AC power is supplied. In such cases, the

power-failure broadcast takes precedence over all other broadcasts.
When the AC power is supplied, 24 VDC is not output from the emergency power supply panel's control
terminal.

• To automatically inspect the battery for power-failure general/attenuator-free broadcasts, connect the battery

check terminal and VOLT DOWN terminal in the same manner as the emergency power supply panel.
This applies to both connection examples of Connection diagrams 1 and 2.

Attenuator-free
broadcast switch

Attenuator-free input

24 VDC

(+)

(-)

Busy output

Output

Digital announcer, etc.

JP-0410

To EP-0510 attenuator-free
broadcast input

Emergency power supply panel for power-failure
general broadcast/attenuator-free broadcast

Connection diagram 2

To power amplifier 24 VDC