2. CONNECTIONS OF INTEGRATED REMOTE CONTROL UNIT RM-971

2.1. Connection Method

• Use heat-resistant, shielded twisted-paired cables for connection.

• Connect between the front-mounted terminal block of Junction Panel JP-0410 and the terminal block of the

remote control unit.

2.2. Notes on Connections

The maximum cable distance between the main rack and the remote control unit is 800 m, and there is a
limitation to the cable length depending on the type and zone numbers of the connected remote control unit.

2.2.1. Maximum line resistance

EF

(FA)

EMG
ACTI

CPU

OFF

C

H

GND

24V

GND

24V

BATT 1 BATT 2 CHECK GND

MONITOR

1 EMG RM 24V 2 EMG RM 24V

DS CHECK

C1

H1

C2

H2

C3

H3

C4

H4

(-)1

(+)1

(-)2

(+)2

(-)3

(+)3

(-)4

(+)4

GND

EMG REMOTE BUS

EMG REMOTE AUDIO IN

REMOTE OUT

C

H

C

H

RM BUS

EMG
ACTI

CPU

CTRL OFF

MONITOR

24 VDC

POWER GND

JP-0410 front-mounted upper row terminal block

Remote control unit's terminal block

Control line

Power supply line

No. of zones

10 zones

20 zones

30 zones

40 zones

50-90 zones

Over 100 zones

Power cable (1 pair)

Under 5

Under 3

Under 2.5

Under 1.5

Under 1

Under 0.5