About the ep-0510's status outputs – Toa FS-971 SERIES User Manual

Page 34

Advertising
background image

Status to Turn Output On

Warning Announcement or other audio alarm other than the second
signal is being output.

Warning Announcement indicator is on or flashing during or before
and after Warning Announcement.

Evacuation Announcement indicator is on or flashing during or before
and after Evacuation Announcement.

False Alarm Announcement indicator is on or flashing during or
before and after False Alarm Announcement.

Emergency announcement is being made from the PA microphone.

Communication error with the emergency remote control unit or other
irregularity has occurred and the failure indication is being displayed.

General broadcast is being made from any connected equipment.

Equipment do not correctly operate because of writing or overall
check.

34

8. ABOUT THE EP-0510'S STATUS OUTPUTS

These outputs show the status of the Integrated Control Panel EP-0510, and each output turns on when in the
following states.

Signals from these outputs are provided from the status output connector (10-pole SM connector) located on
the EP-0510's rear panel. Pins of the connector are arranged as follows.

Output Name

Audio Alarm Output On

Warning Announcement On

Evacuation Announcement On

False Alarm Announcement On

Microphone Announcement On

Abnormality In Progress

General Broadcast On

System Check In Progress

1

2

3

4

5

6

7

8

9

10

EP-0510

Pin No.

Status output connector

(10-pole SM connector)

Pin No.

Signal Name

Rating

1 Ground

2

Audio Alarm Output On

Withstand voltage: 24 VDC, Current capacity: 0.1 A

3

Warning Announcement On

Withstand voltage: 24 VDC, Current capacity: 0.1 A

4

Evacuation Announcement On

Withstand voltage: 24 VDC, Current capacity: 0.1 A

5

False Alarm Announcement On

Withstand voltage: 24 VDC, Current capacity: 0.1 A

6

Microphone Announcement On

Withstand voltage: 24 VDC, Current capacity: 0.1 A

7

Abnormality In Progress

Withstand voltage: 24 VDC, Current capacity: 0.1 A

8

General Broadcast On

Withstand voltage: 24 VDC, Current capacity: 0.1 A

9

System Check In Progress

Withstand voltage: 24 VDC, Current capacity: 0.1 A

10

+5 V

Current capacity: 1 mA