Use and operation, Installing in a vacuum system, Notice – VACUUBRAND PC 301 User Manual

Page 20

Advertising
background image

Documents are only to be used and distributed completely and unchanged. It is strictly the users´ responsibility to check carefully

the validity of this document with respect to his product. Manual-no.: 999147 / 17/06/2014

page 20 of 40

Use and operation

Installing in a vacuum system

If dangerous or polluting fluids could be released at the outlet, install an appropri-

ate system to catch and dispose of those fluids.

Connect a gas-tight exhaust line at the pump outlet if necessary. Always vent

exhaust gases appropriately (e.g., into a fume hood).

Never block the gas outlet. The exhaust line must always be free of obstructions

(no back pressure) to ensure an unimpeded discharge of gas. The cross-section

of the outlet tubing must be at least the size of the pump’s exhaust connection.

Particles and dust must not be aspirated. If necessary, you must install appropri-

ate filters. You must ensure their suitability concerning gas flow, chemical resist-

ance and resistance to clogging prior to use.

Make sure ventilation is adequate, especially if the pump is installed in an enclo-

sure, or if the ambient temperature is elevated. Provide external ventilation, if nec-

essary.

• Reduce the transmission of vibration. Prevent mechanical load due to rigid pipe-

lines. Insert elastic hoses or flexible elements as couplings between the pump

and rigid pipes.

Note: Flexible elements will compress or flatten when evacuated

if not designed for use under vacuum.

• Hose connections at the pump inlet must always be gas tight.

• A power failure may cause accidental ventilation of the pump, especially if the

gas ballast valve is open. If this constitutes a potential source of danger, take ap-

propriate safety measures.

• Check the power source and the pump’s rating plate to be sure that the power

source and the equipment match in voltage, phase, and frequency.

Make sure ventilation is adequate to maintain recommended operating temperature.

Keep a minimum distance of 5 cm between the cooling fan and surrounding items

(e.g., housing, walls, etc.), or else install an external automatic ventilation system.

Use connecting hoses with large diameter and keep them as short as possible to

avoid flow losses. Locate the pump as closely as possible to the application.

Always install outlet tubing descending from the pump or provide other measures to

avoid backflow of condensate towards the pump.

Recommended: Close flow control diaphragm to isolate the pump from the vacuum

system to allow the pump to warm up before condensable vapours are pumped or to

clean the pump before it is switched off.

When assembling, ensure

vacuum-tightness. After assembly, check the whole sys-

tem for leaks.

Secure hose connections at the pump appropriately, e.g., with hose clamps, to pro-

tect against accidental detachment.

To reduce pump noise emanating from the pump exhaust port, connect an exhaust

hose or use a silencer (see ”Accessories”).

Use the manual flow control diaphragm to control the pumping speed of the pump

and thus the pressure inside the vacuum application. Open the diaphragm: turn in

direction ”+”, pumping speed increases. Closing the diaphragm: turn in direction ”-”,

pumping speed is decreased.

NOTICE

Advertising