CPG #2561255

F

IRE

L

ARM

2500 Operating Manual


3-2

3.2.5

Requirements for Central Station Fire Alarm Systems

• Connect both phone lines to the optional ZDACT and OPLCD and program the telephone

numbers for the reporting station.

• Set the AC trouble report delay from 6 to 12 hours.

3.3

Installing the cabinet (and optional bezel)

1. The

F

IRE

L

ARM

2500 unit may be surface mounted or

semi-flush mounted using the optional trim bezel.

2. The unit should be mounted in a convenient location,

approximately 4 feet from the floor where it will be
accessible for testing and servicing.

3. The main circuit board module can be removed before

attempting to mount the cabinet. Disconnect the two wires of
the transformer from P2 on the main board. Remove the
eight Philips head screws and lock washers. Remove the
circuit board.

4. For semi-flush installations mount the housing so that the

front edge protrudes 1" from the finished wall surface.

5. After all conduits and wiring are in place and the wall surface

is completely finished, slide the trim bezel in place and
fasten with four #6-32 x ¼" machine screws and nuts.

DIMENSIONS ARE IN INCHES

19.25

15.25

14

290-0005

Figure 3-1. Surface mounting dimensions

Figure 3-2. Semi-flush mounting dimensions

Figure 3-3. Trim bezel dimensions