Style Z (Class A) Module for NAC circuits (CAM)

UL LISTED: For use with the FireLarm 2500

Part No. 345-0234
TRANSIENT PROTECTED
BUILT IN 5.1K END OF LINE RESISTOR
POWER REQUIREMENTS IN ALARM: Approx. 25mA @ 24VDC from control panel notification
appliance circuit

The Model CAM Style Z (Class A) Module is designed to be used with the FireLarm 2500 Fire Control
Panels to convert a single Style Y (Class B) notification appliance circuit to a Style Z (Class A) circuit (one
module is required for each notification appliance circuit). The module is provided with snap track which is
mounted to the cabinet via double-sided foam tape and secured by two #6 sheet metal screws. The
module should be mounted in the area below the main circuit module as shown below so that the
terminals are accessible.

NON-POWER LIMITED SIDE

POWER LIMITED SIDE

POWER LIMITED SIDE

290-0023

CAM

MODULES

USE FOAM TAPE TO MOUNT SNAP
TRACK IN CABINET AND SECURE
WITH TWO #6 SHEET METAL
SCREWS BEFORE MOUNTING CAM
MODULE IN SNAP TRACK

2"

5.5"

1

+

+

3

2

-

-

+

4

-

EXTERNAL

INDICATING

APPLIANCES

RED

BLACK

TO INDICATING
APPLIANCE CIRCUIT
TERMINALS.
REMOVE EOL RESISTOR.
POLARITY SHOWN IS FOR
STANDBY (NON-ALARM)
CONDITION

290-0029

CAM

Figure A-4. CAM Module Location.

Figure A-3. CAM Module Wiring.