Ed c b a, Appendix a. optional accessories – CPG FIRELARM 2500 CPG #2561255 User Manual

Page 31

Advertising
background image

E

D

C

B

A

CPG #2561255

F

IRE

L

ARM

2500 Operating Manual

A-1

Appendix A. Optional Accessories

A.1

Remote Annunciator with Liquid Crystal Display (2500-RALCD)

Part # 2500-RALCD
UL Listed: For use with the FireLarm 2500
Dimensions: 4 ½” W X 4 ½” H X 7/8” D (approximate)
Weight: 5.5 OZ.
Enclosure: Stainless steel plate. Mounts on standard double-gang switch box or 4” square box
using adapter plate.
Power Requirements: 24VDC @ 115mA max. – Obtained from control panel.
Line resistance: 25 ohms max


The Model RALCD is a Remote Annunciator that is designed to operate with the FireLarm 2500 Fire
Control Panel. This unit will mount on a standard 2-gang switch box. The LCD displays the same
information as on the main panel. A built in buzzer sounds when a trouble condition exists on the panel.

Two annunciators can be connected in parallel. Jumper SW7 must be shorted to specify annunciator 1,
and must be open to specify annunciator 2.

Keypad – operates the same as on the panel except as noted below.

Key Function Control

When

Active

ACK

Silences buzzer on RALCD only.

Annunciator

Always

TEST

Turns on buzzer, backlight (if off), and scrolls through
alphabet.

Annunciator Always

RESET

Resets all alarm circuits if condition has been corrected,
removes power from initiating device circuit and auxiliary
power from smoke detectors for 7 seconds.

Panel

Key switch on

DRILL

Pressing for 2 seconds will initiate a fire drill.

Panel

Key switch on

SCROLL Scrolls through trouble conditions, if present.

Panel

Key switch on

SILENCE Press once to silence buzzers on panel and annunciators.

Press again to silence signal circuits.

Panel

Key switch on

Electrical Connections
RALCD Terminal

Function of Terminal

FireLarm 2500 Terminal (TB4)

D Data

signal

D

D*

Data inverted signal

D*

GND Power

ground

GND

+24 VDC

Power

+24 VDC

EARTH

Earth ground (optional connection) E

Fire Alarm Annunciator

LIQUID CRYSTAL

DISPLAY

KEY SWITCH

KEY SWITCH

CONTROL

OFF

TEST

SCROLL

SILENCE

DRILL

HOLD 2 SECS

ACK

RESET

290-0011

Figure A-1. LCD Remote Annunciator