5 maintenance – CPG FIRELARM 2500 CPG #2561255 User Manual

Page 29

Advertising
background image

E

D

C

B

A

5

CPG #2561255

F

IRE

L

ARM

2500 Operating Manual

5-1

5 Maintenance

Most modern control units do not require periodic adjustment or field repair other than replacement of a
module or printed circuit board assembly. Defective printed circuit board assemblies or modules can best
be serviced at the manufacturer’s plant or at their authorized service facility. Where the control unit uses
printed circuit boards, care should be taken to clean off excessive dust. The boards should be maintained
clean and dry to ensure proper operation.

5.1

Auto Reset feature (One-man test)

This function only works when the panel is in the standby mode. Pressing



sets the panel into one-

man test mode. When a zone goes into alarm, the audible circuits are pulsed ½ second for identification
of the zone; i.e. zone 1 has one pulse, zone 2 has two pulses, etc. After the zone number is pulsed, the
panel automatically resets the zones by cycling power. After 15 minutes of no activity, the panel provides
5 pulses on the NAC and goes back into standby condition. Pressing



again (no pulses with this

exit) returns the panel to standby condition.

5.2

Inspection and Test procedure

5.2.1

Testing the control panel


Notify the building occupants, the fire department and/or receiving station personnel before and after
testing is performed. Notify the fire department and/or other receiving station personnel if alarm,
supervisory, and/or trouble signals are transmitted. (Transmissions may be inhibited by pressing



.)

 In addition to the testing procedures described below, the FireLarm

2500 system and all of its associated protective signaling adjuncts
should be inspected and tested in accordance with the NFPA-72
National Fire Alarm Code and any requirements of the Authority Having
Jurisdiction.

1. Notify the proper building personnel so audible and/or visual signals can be viewed as a test by

building occupants.

2. Press

. This will cause all audible and visual indicators on the panel and the NAC outputs to

come on. Releasing

will restore the panel to the condition it was in prior to operation of this

touchpad.

3. Press

each



. This will result in a trouble condition and operate all indicators as described in

section 2.5.5 Initiating Zone Trouble. Repressing



will restore all indicators to normal.

4. Momentarily open each of the following circuits. Observe that each of these results in a trouble

condition and appropriate indicators operate as described in the section for the particular circuit that is
faulted. (See section 2.5.5 Initiating Zone Trouble)

• Each initiating device zone (there is a brief delay when these circuits are in the Style

D (Class A) mode.

• Supervisory

circuit.

• Notification

appliance

circuit

5. Momentarily shunt each of the circuits listed in the previous step (except the supervisory circuit) with

4.7K ohm resistor and again observe that a trouble condition is generated for each test. Use 1.5K
ohm for the supervisory circuit.

6. Turn off the AC power at the circuit breaker panel. The green AC-ON indicator will be extinguished.

Observe that all the trouble indications occur that are described in section 2.5.10 AC power
conditions
.

Advertising