2500 Operating Manual

3-7

3.8

Notification Appliance Circuits Connections


The control panel has two Style Y (Class B) notification appliance circuits which can be upgraded to Style
Z (class A) by the addition of a model CAM (Class A Module). One module is required for each circuit that
is to be upgraded. See Appendix A for more information.

The notification appliance circuits are power limited, regulated 24 VDC rated at 2.0 amperes max each.
(Total system current not to exceed 2.5 A.)

 Notes for Figure 3-7:
1.

Power inputs (not power limited). Wire wrap to standoff for strain relief.

2.

Battery leads (not power limited).

3.

Use left hand knockouts for non-power limited wiring.

4.

Use right hand knockouts for power limited wiring.

5.

Connect earth ground to corner of main board using a #6 ring terminal or wire and
ring provided.

6.

All wiring must be wire-wrapped to a standoff or other mechanically secure location.

 All field-installed wiring connected to this panel must maintain a spacing of ¼

inch between all power-limited conductors and all electrical light, power,
Class 1, or non-power limited conductors.

Figure 3-7. Wire Routing

Diagram

NON-POWER LIMITED SIDE

POWER LIMITED SIDE

NON-POWER LIMITED SIDE

POWER LIMITED SIDE

290-0009

POWER IN

SEE NOTE 1

POWER

CONNECTIONS

(120VAC)

GROUND SCREW

SEE NOTE 5

POWER IN

SEE NOTE 1

POWER IN

SEE NOTE 1

SEE NOTE 4