Carrier COBRA 48/50HJ004-014 User Manual

Page 13

Advertising
background image

13

NOTE: For wire runs up 50 ft, use no. 18 AWG (American Wire
Gage) insulated wire (35 C minimum). For 50 to 75 ft, use no.
16 AWG insulated wire (35 C minimum). For over 75 ft, use no.
14 AWG insulated wire (35 C minimum). All wire larger than
no. 18 AWG cannot be directly connected to the thermostat and
will require a junction box and splice at the thermostat.

Pass the control wires through the hole provided in the cor-

ner post; then feed wires through the raceway built into the
corner post to the 24-v barrier located on the left side of the

control box. See Fig. 10. The raceway provides the UL
required clearance between high- and low-voltage wiring.
NOTE: A humidistat and a temperature sensor can be used in
place of a thermidistat for PremierLink™ units.
HEAT ANTICIPATOR SETTINGS — Set heat anticipator
settings at .14 amp for the first stage and .14 amp for second-
stage heating, when available.

Table 1A — Electrical Data (COBRA™ Energy Recovery 48HJ004-007 Units with 62AQ060)

LEGEND

*Used to determine minimum disconnect per NEC.

†Single point box CRSINGLE017A00 is part of base unit.

NOTES:
1. In compliance with NEC requirements for multimotor and combination load

equipment (refer to NEC Articles 430 and 440), the overcurrent protective
device for the unit shall be fuse or HACR breaker. UL, Canada units may be
fuse or circuit breaker.

2. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is
greater than 2%.
Use the following formula to determine the percent of volt-
age imbalance.

Example: Supply voltage is 460-3-60.

AB = 452 v
BC = 464 v
AC = 455 v

= 457

Determine maximum deviation from average voltage.

(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v

Maximum deviation is 7 v.
Determine percent of voltage imbalance.

% Voltage Imbalance = 100 x

= 1.53%

This amount of phase imbalance is satisfactory as it is below the maximum
allowable 2%.

UNIT

NOMINAL

V-PH-Hz

IFM

TYPE

CONV

OUTLET

62AQ

FLA

POWER SUPPLY

DISCONNECT SIZE*

MCA

FUSE OR

HACR BKR

FLA

LRA

48HJ004

208/230-1-60

STD

NO

9.2

34.8/34.8

40/40

35/35

135/135

STD

YES

9.2

40.8/40.8

45/45

41/41

140/140

208/230-3-60

STD

NO

9.2

27.7/27.7

35/35

29/29

124/124

STD

YES

9.2

33.7/33.7

40/35

34/34

129/129

HIGH STATIC

NO

9.2

28.6/28.6

35/35

30/30

154/154

HIGH STATIC

YES

9.2

34.6/34.6

40/40

35/35

158/158

460-3-60

STD

NO

9.2

13.6

20

14

63

STD

YES

9.2

16.3

20

20

67

HIGH STATIC

NO

9.2

14.0

20

15

77

HIGH STATIC

YES

9.2

16.7

20

20

82

48HJ005

208/230-1-60

STD

NO

9.2

44.4/44.4

60/60

44/44

173/173

STD

YES

9.2

50.4/50.4

60/60

50/50

178/178

208/230-3-60

STD

NO

9.2

31.7/31.7

40/40

33/33

140/140

STD

YES

9.2

37.7/37.7

40/40

38/38

145/145

HIGH STATIC

NO

9.2

32.6/32.6

40/40

34/34

170/170

HIGH STATIC

YES

9.2

38.6/38.6

45/45

39/39

174/174

460-3-60

STD

NO

9.2

15.2

20

16

70

STD

YES

9.2

17.9

20

21

75

HIGH STATIC

NO

9.2

15.6

20

16

84

HIGH STATIC

YES

9.2

18.3

20

22

89

48HJ006

208/230-1-60

STD

NO

9.2

55.5/55.5

70/70

56/56

250/250

STD

YES

9.2

61.5/61.5

70/70

61/61

255/255

208/230-3-60

STD

NO

9.2

38.1/38.1

45/45

39/39

202/202

STD

YES

9.2

44.1/44.1

50/50

44/44

207/207

HIGH STATIC

NO

9.2

39.8/39.8

45/45

41/41

221/221

HIGH STATIC

YES

9.2

45.8/45.8

50/50

46/46

226/226

460-3-60

STD

NO

9.2

19.3

25

20

101

STD

YES

9.2

22.0

25

25

106

HIGH STATIC

NO

9.2

20.1

25

20

110

HIGH STATIC

YES

9.2

22.8

25

26

115

48HJ007

208/230-3-60

STD

NO

9.2

42.0/42.0

50/50

42/42

234/234

STD

YES

9.2

48.0/48.0

60/60

48/48

239/239

208/230-3-60

HIGH STATIC

NO

9.2

43.7/43.7

50/50

44/44

253/253

HIGH STATIC

YES

9.2

49.7/49.7

60/60

50/50

258/258

460-3-60

STD

NO

9.2

19.8

25

20

114

STD

YES

9.2

22.5

25

26

118

HIGH STATIC

NO

9.2

20.6

25

21

123

HIGH STATIC

YES

9.2

23.3

30

26

128

FLA

Full Load Amps

HACR — Heating, Air Conditioning and Refrigeration
IFM

Indoor (Evaporator) Fan Motor

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection
NEC

National Electrical Code

UL

Underwriters’ Laboratories

= 100 x

max voltage deviation from average voltage

average voltage

Average Voltage =

452 + 464 + 455

3

=

1371

3

IMPORTANT: If the supply voltage phase imbalance is more than 2%, con-
tact your local electric utility company immediately.

7
457

Advertising