Carrier COBRA 48/50HJ004-014 User Manual

Page 19

Advertising
background image

19

Table 1D — Electrical Data (COBRA™ Energy Recovery 50HJ004-007 Units with 62AQ100) (cont)

LEGEND

*Used to determine minimum disconnect per NEC.

†Single point box CRSINGLE017A00 is part of base unit.

NOTES:
1. In compliance with NEC requirements for multimotor and combination load

equipment (refer to NEC Articles 430 and 440), the overcurrent protective device
for the unit shall be fuse or HACR breaker. UL, Canada units may be fuse or cir-
cuit breaker.

2. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is greater
than 2%.
Use the following formula to determine the percent of voltage
imbalance.

Example: Supply voltage is 460-3-60.

AB = 452 v
BC = 464 v
AC = 455 v

= 457

Determine maximum deviation from average voltage.

(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v

Maximum deviation is 7 v.
Determine percent of voltage imbalance.

% Voltage Imbalance

= 100 x

= 1.53%

This amount of phase imbalance is satisfactory as it is below the maximum allow-
able 2%.

UNIT

NOMINAL

V-PH-Hz

IFM

TYPE

CONV

OUTLET

62AQ

FLA

HEATER

CRHEATER

---A00

HEAT

POWER SUPPLY

SINGLE

POINT BOX

CRSINGLE

---A00

DISCONNECT SIZE*

FLA

MCA

FUSE OR

HACR BKR

MOCP

FLA

LRA

50HJ005

(cont)

460-3-60

STD

YES

15.1

NONE

20.9

25

25

88

006

7.2

22.2

30

25

88

008

13.8

30.5

35

025

25

88

009

16.8

34.2

40

025

35

88

008+008

27.7

47.7

50

025

48

96

HIGH STATIC

NO

15.1

NONE

18.6

25

19

97

006

7.2

20.5

25

19

98

008

13.8

28.8

35

025

19

98

009

16.8

32.5

35

025

31

98

008+008

27.7

46.0

50

025

43

108

HIGH STATIC

YES

15.1

NONE

21.3

25

25

102

006

7.2

22.6

30

25

103

008

13.8

30.9

35

025

25

103

009

16.8

34.6

40

025

36

103

008+008

27.7

48.1

50

025

48

110

50HJ006

208/230-1-60

STD

NO

15.1

NONE

—/—

61.4/ 61.4

70/70

62/ 62

276/276

002

23.5/27.1

61.4/ 61.4

70/ 70

004

62/ 62

276/276

003

31.4/36.3

65.8/ 71.8

70/ 80

004

64/ 69

276/276

002+002

46.9/54.2

85.2/ 94.2

90/100

005

81/ 90

276/276

003+003

62.8/72.5

105.1/117.2

110/125

005

100/111

276/276

004+004

75.8/87.5

121.3/135.9

125/150

005

115/128

276/276

STD

YES

15.1

NONE

—/—

67.4/ 67.4

80/80

68/ 68

281/281

002

23.5/27.1

67.4/ 67.4

80/ 80

004

68/ 68

281/281

003

31.4/36.3

70.6/ 76.0

80/ 80

005

69/ 74

281/281

002+002

46.9/54.2

90.0/ 98.4

90/100

005

87/ 95

281/281

003+003

62.8/72.5

109.9/121.4

110/125

005

105/116

281/281

004+004

75.8/87.5

126.1/140.1

150/150

005

120/133

281/281

208/230-3-60

STD

NO

15.1

NONE

—/—

44.0/ 44.0

50/50

46/ 46

228/228

002

13.6/15.6

44.0/ 44.0

50/50

46/ 46

228/228

004

21.9/25.3

50.9/ 55.1

60/60

49/ 53

228/228

005

33.4/38.5

65.2/ 71.6

70/ 80

002

62/ 68

228/228

004+004

43.8/50.5

78.2/ 86.7

80/ 90

003

74/ 82

228/228

004+005

55.2/63.8

92.6/103.2

100/110

003

88/ 97

228/228

STD

YES

15.1

NONE

—/—

50.0/ 50.0

60/60

51/ 51

233/233

002

13.6/15.6

50.0/ 50.0

60/60

51/ 51

233/233

004

21.9/25.3

55.7/ 59.3

70/ 70

002

55/ 58

233/233

005

33.4/38.5

70.0/ 75.8

80/ 80

003

68/ 73

233/233

004+004

43.8/50.5

83.0/ 90.9

90/100

003

80/ 87

233/233

004+005

55.2/63.8

97.4/107.4

100/110

003

93/102

233/233

HIGH STATIC

NO

15.1

NONE

—/—

45.7/ 45.7

60/60

48/ 48

247/247

002

13.6/15.6

45.7/ 45.7

60/60

48/ 48

247/247

004

21.9/25.3

52.6/ 56.8

60/ 70

002

51/ 55

247/247

005

33.4/38.5

66.9/ 73.3

70/ 80

002

64/ 70

247/247

004+004

43.8/50.5

79.9/ 88.4

80/ 90

003

76/ 84

247/247

004+005

55.2/63.8

94.3/104.9

100/110

003

90/ 99

247/247

HIGH STATIC

YES

15.1

NONE

—/—

51.7/ 51.7

60/60

53/ 53

252/252

002

13.6/15.6

51.7/ 51.7

60/60

53/ 53

252/252

004

21.9/25.3

57.4/ 61.0

70/ 70

002

57/ 60

252/252

005

33.4/38.5

71.7/ 77.5

80/ 80

003

70/ 75

252/252

004+004

43.8/50.5

84.7/ 92.6

90/100

003

82/ 89

252/252

004+005

55.2/63.8

99.1/109.1

100/110

003

95/104

252/252

460-3-60

STD

NO

15.1

NONE

22.2

25

23

114

006

7.2

22.2

25

23

114

008

13.8

28.8

35

025

23

114

009

16.8

32.5

35

025

31

114

008+008

27.7

46.0

50

025

43

114

008+009

30.7

49.8

50

025

47

114

FLA

Full Load Amps

HACR — Heating, Air Conditioning and Refrigeration
IFM

Indoor (Evaporator) Fan Motor

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection
NEC

National Electrical Code

UL

Underwriters’ Laboratories

= 100 x

max voltage deviation from average voltage

average voltage

Average Voltage =

452 + 464 + 455

3

=

1371

3

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact
your local electric utility company immediately.

7
457

Advertising