Carrier COBRA 48/50HJ004-014 User Manual

Page 5

Advertising
background image

5

Fig. 3B — Roof Curb Details (48/50HJ008-014 Section Only)

TO ENSURE AN AIRTIGHT CONNECTION,
PLACE UNIT ON CURB AS CLOSE TO
DUCT END AS POSSIBLE.

TO ENSURE AN AIRTIGHT CONNECTION,
PLACE UNIT ON CURB AS CLOSE TO
DUCT END AS POSSIBLE.

NOTES:

1. Roof curb accessory is shipped disassembled.
2. Insulated panels: 1-in. thick polyurethane foam,

1

3

/

4

lb density.

3. Dimensions in [

] are in millimeters.

4. Roof curb: 16-gage steel.
5. Attach ductwork to curb (flanges of duct rest on

curb).

6. Service clearance 4 ft on each side.

7.

Direction of airflow.

8. Connector packages CRBTMPWR001A00 and

2A00 are for thru-the-curb gas type. Packages
CRBTMPWR003A00 and 4A00 are for thru-
the-bottom type gas connections.

ROOF CURB

ACCESSORY

“A”

UNIT SIZE

48/50HJ

CRRFCURB003A00

1

′-2″ [356]

008-014

CRRFCURB004A00

2

′-0″ [610]

CONNECTOR

PKG. ACCY.

B

C

D ALT

DRAIN

HOLE

GAS

POWER

CONTROL

CRBTMPWR001A00

2

′-8

7

/

16

[827]

1

′-10

15

/

16

[583]

1

3

/

4

[44.5]

3

/

4

[19] NPT

3

/

4

″ [19] NPT

1

/

2

[12.7] NPT

CRBTMPWR002A00

1

1

/

4

″ [31.7]

CRBTMPWR003A00

1

/

2

[12.7] NPT

3

/

4

″ [19] NPT

1

/

2

[12.7] NPT

CRBTMPWR004A00

3

/

4

[19] NPT

1

1

/

4

″ [31.7]

Advertising