Table 1D — Electrical Data (COBRA™ Energy Recovery 50HJ004-007 Units with 62AQ100) (cont)

LEGEND

*Used to determine minimum disconnect per NEC.

†Single point box CRSINGLE017A00 is part of base unit.

NOTES:
1. In compliance with NEC requirements for multimotor and combination load

equipment (refer to NEC Articles 430 and 440), the overcurrent protective device
for the unit shall be fuse or HACR breaker. UL, Canada units may be fuse or cir-
cuit breaker.

2. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is greater
than 2%.
Use the following formula to determine the percent of voltage
imbalance.

Example: Supply voltage is 460-3-60.

AB = 452 v
BC = 464 v
AC = 455 v

= 457

Determine maximum deviation from average voltage.

(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v

Maximum deviation is 7 v.
Determine percent of voltage imbalance.

% Voltage Imbalance

= 100 x

= 1.53%

This amount of phase imbalance is satisfactory as it is below the maximum allow-
able 2%.

UNIT

NOMINAL

V-PH-Hz

IFM

TYPE

CONV

OUTLET

62AQ

FLA

HEATER

CRHEATER

---A00

HEAT

POWER SUPPLY

SINGLE

POINT BOX

CRSINGLE

---A00

DISCONNECT SIZE*

FLA

MCA

FUSE OR

HACR BKR

MOCP

FLA

LRA

50HJ006

(cont)

460-3-60

STD

YES

15.1

NONE

24.9

30

28

119

006

7.2

24.9

30

28

119

008

13.8

30.9

35

025

28

119

009

16.8

34.6

40

025

36

119

008+008

27.7

48.1

50

025

48

119

008+009

30.7

51.9

60

025

52

119

HIGH STATIC

NO

15.1

NONE

23.0

30

24

123

006

7.2

23.0

30

24

124

008

13.8

29.6

35

025

24

124

009

16.8

33.3

35

025

32

124

008+008

27.7

46.8

50

025

44

124

008+009

30.7

50.6

60

025

48

124

HIGH STATIC

YES

15.1

NONE

25.7

30

29

128

006

7.2

25.7

30

29

129

008

13.8

31.7

35

025

29

129

009

16.8

35.4

40

025

37

129

008+008

27.7

48.9

50

025

49

129

008+009

30.7

52.7

60

025

53

129

50HJ007

208/230-3-60

STD

NO

15.1

NONE

—/—

47.9/ 47.9

60/60

49/ 49

260/260

002

13.6/15.6

47.9/ 47.9

60/60

49/ 49

260/260

004

21.9/25.3

50.9/ 55.1

60/60

49/ 53

260/260

005

33.4/38.5

65.2/ 71.6

70/ 80

002

62/ 68

260/260

004+004

43.8/50.5

78.2/ 86.7

80/ 90

003

74/ 82

260/260

004+005

55.2/63.8

92.6/103.2

100/110

003

88/ 97

260/260

STD

YES

15.1

NONE

—/—

53.9/ 53.9

60/60

55/ 55

265/265

002

13.6/15.6

53.9/ 53.9

60/60

55/ 55

265/265

004

21.9/25.3

55.7/ 59.3

70/ 70

002

55/ 58

265/265

005

33.4/38.5

70.0/ 75.8

80/ 80

003

68/ 73

265/265

004+004

43.8/50.5

83.0/ 90.9

90/100

003

80/ 87

265/265

004+005

55.2/63.8

97.4/107.4

100/110

003

93/102

265/265

HIGH STATIC

NO

15.1

NONE

—/—

49.6/ 49.6

60/60

51/ 51

279/279

002

13.6/15.6

49.6/ 49.6

60/60

51/ 51

279/279

004

21.9/25.3

52.6/ 56.8

60/ 70

002

51/ 55

279/279

005

33.4/38.5

66.9/ 73.3

70/ 80

002

64/ 70

279/279

004+004

43.8/50.5

79.9/ 88.4

80/ 90

003

76/ 84

279/279

004+005

55.2/63.8

94.3/104.9

100/110

003

90/ 99

279/279

HIGH STATIC

YES

15.1

NONE

—/—

55.6/ 55.6

60/60

57/ 57

284/284

002

13.6/15.6

55.6/ 55.6

60/60

57/ 57

284/284

004

21.9/25.3

57.4/ 61.0

70/ 70

002

57/ 60

284/284

005

33.4/38.5

71.7/ 77.5

80/ 80

003

70/ 75

284/284

004+004

43.8/50.5

84.7/ 92.6

90/100

003

82/ 89

284/284

004+005

55.2/63.8

99.1/109.1

100/110

003

95/104

284/284

460-3-60

STD

NO

15.1

NONE

22.8

30

23

127

006

7.2

22.8

30

23

127

008

13.8

28.8

35

025

23

127

009

16.8

32.5

35

025

31

127

008+008

27.7

46.0

50

025

43

127

008+009

30.7

49.8

50

025

47

127

STD

YES

15.1

NONE

25.5

30

29

131

006

7.2

25.5

30

29

132

008

13.8

30.9

35

025

29

132

009

16.8

34.6

40

025

36

132

008+008

27.7

48.1

50

025

48

132

008+009

30.7

51.9

60

025

52

132

HIGH STATIC

NO

15.1

NONE

23.6

30

24

136

006

7.2

23.6

30

24

137

008

13.8

29.6

35

025

24

137

009

16.8

33.3

35

025

32

137

008+008

27.7

46.8

50

025

44

137

008+009

30.7

50.6

60

025

48

137

HIGH STATIC

YES

15.1

NONE

26.3

30

30

141

006

7.2

26.3

30

30

141

008

13.8

31.7

35

025

30

141

009

16.8

35.4

40

025

37

141

008+008

27.7

48.9

50

025

49

141

008+009

30.7

52.7

60

025

53

141

FLA

Full Load Amps

HACR — Heating, Air Conditioning and Refrigeration
IFM

Indoor (Evaporator) Fan Motor

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection
NEC

National Electrical Code

UL

Underwriters’ Laboratories

= 100 x

max voltage deviation from average voltage

average voltage

Average Voltage =

452 + 464 + 455

3

=

1371

3

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact
your local electric utility company immediately.

7
457

Advertising