Table 2 — Light Commercial Thermidistat (LCT) Operating Sequence and System Response

LEGEND

*Unless unit compressor has been rewired as described in Step 11 (page 29).

UNOCCUPIED

COOLING

ER Comp

ER Fans

RT Comp 1

RT Comp 2

RT Fans

RT Heat

Indoor Temperature Above 2nd Stage
Set Point

Humidity Low & OAT Low

On

On (cyc.)

On w/o MM

Off

On (cyc.)

Off

Humidity Low & OAT High

Off

Off

On w/o MM

w/o MM

On (cyc.)

Off

Humidity High & OAT Low

Off

Off

On w MM

On w MM

On (cyc.)

Off

Humidity High & OAT High

Off

Off

On w MM

On w MM

On (cyc.)

Off

Indoor Temperature Between 1st and
2nd Stage Set Points

Humidity Low & OAT Low

Off

On (cyc.)

Off

Off

On (cyc.)

Off

Humidity Low & OAT High

Off

Off

On w/o MM

Off

On (cyc.)

Off

Humidity High & OAT Low

Off

Off

On w MM

Off

On (cyc.)

Off

Humidity High & OAT High

Off

Off

On w MM

Off

On (cyc.)

Off

Indoor Temperature Below 1st Stage
Set Point

Off

Off

Off

Off

Off

Off

NOTE: OAT < 55° all compression off*

HEATING

ER Comp.

ER Fans

RT Comps.

RT Fans

RT Heat

Indoor Temperature Above 1st Set
Point

Off

Off

Off

Off

Off

Indoor Temperature Between 1st and
2nd Stage Set Points

Off

Off

Off

On (cyc.)

On, 50%

Indoor Temperature Below 2nd Stage
Set Point

Off

Off

Off

On (cyc.)

On, 100%

OCCUPIED

COOLING

ER Comp

ER Fans

RT Comp 1

RT Comp 2

RT Fan

RT Heat

Indoor Temperature Above 2nd Stage
Set Point

Humidity Low & OAT Low

On

On

On w/o MM

On w/o MM

On

Off

Humidity Low & OAT High

On

On

On w/o MM

On w/o MM

On

Off

Humidity High & OAT Low

On

On

On w MM

On w MM

On

Off

Humidity High & OAT High

On

On

On w MM

On w MM

On

Off

Indoor Temperature Between 1st and
2nd Stage Set Points

Humidity Low & OAT Low

Off

On

Off

Off

On

Off

Humidity Low & OAT High

On

On

On w/o MM

Off

On

Off

Humidity High & OAT Low

On

On

On w MM

Off

On

Off

Humidity High & OAT High

On

On

On w MM

Off

On

Off

Indoor Temperature Below 1st Stage
Set Point

Humidity Low

Off

On

Off

Off

On

Off

Humidity High

On

On

Off

Off

On

Off

NOTE: OAT < 55° all compression off*

HEATING

ER Comp

ER Fans

RT Comps

RT Fans

RT Heat

Indoor Temperature Above 1st Stage
Set Point

Off

On

Off

On

Off

Indoor Temperature Between 1st and
2nd Stage Set Points

OAT >Set Pt

On

On

Off

On

Off

OAT <Set Pt

On

On

Off

On

On, 50%

Indoor Temperature Below 2nd Stage
Set Point

OAT >Set Pt

On

On

Off

On

On, 50%

OAT <Set Pt

On

On

Off

On

On, 100%

Comp — Compressor
ER

Energy Recovery section

MM

MoistureMi$er™ Dehumidification Device

OAT

Outdoor-Air Temperature

RT

Rooftop Unit

Set Pt — Set Point