Carrier COBRA 48/50HJ004-014 User Manual

Page 26

Advertising
background image

26

Table 1H — Electrical Data (COBRA™ Energy Recovery 50HJ008-014 Units with 62AQ300) (cont)

LEGEND

*Used to determine minimum disconnect per NEC.

†Single point box CRSINGLE017A00 is part of base unit.

NOTES:
1. In compliance with NEC requirements for multimotor and combination load equipment

(refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall
be fuse or HACR breaker. UL, Canada units may be fuse or circuit breaker.

2. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is greater than 2%.
Use the following formula to determine the percent of voltage imbalance.

Example: Supply voltage is 460-3-60.

AB = 452 v
BC = 464 v
AC = 455 v

= 457

Determine maximum deviation from average voltage.

(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v

Maximum deviation is 7 v.
Determine percent of voltage imbalance.

% Voltage Imbalance

= 100 x

= 1.53%

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

UNIT

NOMINAL

V-PH-Hz

IFM

TYPE

CONV

OUTLET

62AQ

FLA

HEATER

CRHEATER

---A00

HEAT

POWER SUPPLY

SINGLE

POINT BOX

CRSINGLE

---A00

DISCONNECT SIZE*

FLA

MCA

FUSE OR

HACR BKR

MOCP

FLA

LRA

50HJ012

208/230-3-60

STD

NO

29.8

NONE

—/—

82.8/ 82.8

90/ 90

90/ 90

519/519

017

21.7/ 25.0

82.8/ 82.8

90/ 90

90/ 90

519/519

010

33.4/ 38.5

86.4/ 92.8

100/110

90/ 91

519/519

012

66.7/ 77.0

128.1/140.9

150/150

123/135

519/519

012+017

88.4/102.0

155.2/172.2

175/175

148/164

519/519

010+012

104.2/120.3

175.0/165.0

175/200

166/185

519/519

STD

YES

29.8

NONE

—/—

88.8/ 88.8

100/100

96/ 96

523/523

017

21.7/ 25.0

88.8/ 88.8

100/100

96/ 96

523/523

010

33.4/ 38.5

91.2/ 97.0

110/110

96/ 96

523/523

012

66.7/ 77.0

132.9/145.1

150/150

129/140

523/523

012+017

88.4/102.0

160.0/176.4

175/200

154/169

523/523

010+012

104.2/120.3

179.8/169.2

200/200

172/190

523/523

HIGH STATIC

NO

29.8

NONE

—/—

87.2/ 87.2

100/100

95/ 95

542/542

017

21.7/ 25.0

87.2/ 87.2

100/100

95/ 95

542/542

010

33.4/3 8.5

90.8/ 97.2

100/110

95/ 96

542/542

012

66.7/ 77.0

132.5/145.3

150/150

128/140

542/542

012+017

88.4/102.0

159.6/176.6

175/200

153/169

542/542

010+012

104.2/120.3

179.4/169.4

200/200

171/190

542/542

HIGH STATIC

YES

29.8

NONE

—/—

93.2/ 93.2

100/100

101/101

547/547

017

21.7/ 25.0

93.2/ 93.2

100/100

101/101

547/547

010

33.4/ 38.5

95.6/101.4

110/110

101/101

547/547

012

66.7/ 77.0

137.3/149.5

150/150

134/145

547/547

012+017

88.4/102.0

164.4/180.8

175/200

159/174

547/547

010+012

104.2/120.3

184.2/173.6

200/200

177/195

547/547

460-3-60

STD

NO 15.8

NONE

40.7

45.0

44.0

260.0

016

16.7

45.8

60.0

011

44.0

261.0

013

19.8

49.7

60.0

011

47.0

261.0

014

33.4

66.7

80.0

014

62.0

261.0

014+016

50.2

87.6

100.0

016

81.0

261.0

013+015

60.1

85.0

110.0

016

93.0

261.0

STD

YES

15.8

NONE

43.4

45.0

47.0

262.0

016

16.7

47.9

60.0

014

47.0

263.0

013

19.8

51.8

60.0

011

49.0

263.0

014

33.4

68.8

80.0

014

65.0

263.0

014+016

50.2

89.7

100.0

016

84.0

263.0

013+015

60.1

87.1

110.0

016

95.0

263.0

HIGH STATIC

NO

15.8

NONE

43.3

50.0

47.0

272.0

016

16.7

48.4

60.0

014

47.0

272.0

013

19.8

52.3

60.0

011

50.0

272.0

014

33.4

69.3

80.0

014

65.0

272.0

014+016

50.2

90.2

100.0

016

84.0

272.0

013+015

60.1

87.6

110.0

016

96.0

272.0

HIGH STATIC

YES

15.8

NONE

46.0

50.0

0.0

50.0

274.0

016

16.7

50.5

60.0

014

50.0

274.0

013

19.8

54.4

60.0

011

52.0

274.0

014

33.4

71.4

90.0

014

68.0

274.0

014+016

50.2

92.3

100.0

016

87.0

274.0

013+015

60.1

89.7

110.0

016

98.0

274.0

50HJ014

208/230-3-60

STD

NO

29.8

NONE

—/—

90.4/ 90.4

100/100

98/ 98

604/604

017

21.7/ 25.0

90.4/ 90.4

100/100

98/ 98

604/604

010

33.4/ 38.5

90.8/ 97.2

100/110

98/ 98

604/604

012

66.7/ 77.0

132.5/145.3

150/150

128/140

604/604

012+017

88.4/102.0

159.6/176.6

175/200

153/169

604/604

010+012

104.2/120.3

179.4/169.4

200/200

171/190

604/604

STD

YES

29.8

NONE

—/—

96.4/ 96.4

100/100

104/104

609/609

017

21.7/ 25.0

96.4/ 96.4

100/100

104/104

609/609

010

33.4/ 38.5

95.6/101.4

110/110

104/104

609/609

012

66.7/ 77.0

137.3/149.5

150/150

134/145

609/609

012+017

88.4/102.0

164.4/180.8

175/200

159/174

609/609

010+012

104.2/120.3

184.2/173.6

200/200

177/195

609/609

STD

NO

15.8

NONE

44.9

50.0

49.0

287.0

016

16.7

48.4

60.0

014

49.0

287.0

013

19.8

52.3

60.0

011

50.0

287.0

016

16.7

48.4

70.0

014

49.0

287.0

014+016

50.2

90.2

100.0

016

84.0

287.0

013+015

60.1

87.6

110.0

016

96.0

287.0

STD

YES

15.8

NONE

47.6

50.0

51.0

289.0

016

16.7

50.5

60.0

014

51.0

289.0

013

19.8

54.4

60.0

011

52.0

289.0

016

16.7

50.5

70.0

014

51.0

289.0

014+016

50.2

92.3

100.0

016

87.0

289.0

013+015

60.1

89.7

110.0

016

98.0

289.0

FLA

Full Load Amps

HACR

Heating, Air Conditioning and Refrigeration

IFM

Indoor (Evaporator) Fan Motor

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps

MOCP

Maximum Overcurrent Protection

NEC

National Electrical Code

UL

Underwriters’ Laboratories

= 100 x

max voltage deviation from average voltage

average voltage

Average Voltage =

452 + 464 + 455

3

=

1371

3

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your
local electric utility company immediately.

7
457

Advertising