Siction 11 — installing gas piping, B. installation, Furnace gas entry piping – Bard Bayrd Furnace 403293A User Manual

Page 20

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

18. 10-turn coil of wire

to fit on ammeter

Room thermostat heat
anticipator setting

19.

"U" Tube Water

Manometer with O.V

resolution 0“to 15"
W.C. range

Gas pressure

measurement

20. Slope gauge with

0.01” pressure

measurement taps
and tubing, Oto 1"

W.C. range

Duct work static pressure

21. 2 thermometers

Temperature rise measured

with 1 -degree

through lurnace

Fahrenheit

resolution, 50

degrees F to 175
degrees F range

22. Stop watch

Gas input meter timing

23. Torque wrench

(100 inch-pounds)

Proper screw installation

SICTION 11 — INSTALLING GAS PIPING.

Equipment needed: Save time by getting these tools before
you start: Item number(s) 8,12.13 and 14 listed in Section

10.

A. Preparation.

Gas piping must meet requirements of current National
Fuel Gas Code ANSI Z223.1/NFPA 54 and local codes.
Size of pipe running to furnace depends on:

Length of pipe;

• Number of fittings;
• Specific gravity of gas;

Input requirements fBtuh) of all gas-fired appli­

ances attached to same main supply line.

Refer to current National Fuel Gas Code ANSI Z223.1/
NFPA 54 for correct gas pipe sizing information.

Plan furnace gas supply piping so it will not interfere with
removal of burner assembly, front door or blower door
for servicing.

Always use a pipe thread sealant which is resistant to
propane (LP) gas solvent action. Sparingly apply sealant
to all joints on male threads only, starting two threads
back from end.

B. Installation.

1.

Install A.G.A. listed manual shut-off valve in gas

supply line immediately upstream of furnace. Install

1/8" NPT plugged tapping accessible for test gauge

connection. Omit separate, plugged tapping if local

area accepts plugged tapping in gas control inlet.

2.

After in-line manual shut-off valve, install a drip leg
(sediment trap) at gas supply line inlet connection to

furnace. A convenient way to do this when you have

reduced bottom clearance, is to make drip leg by
using a 1/2" to Г NPT Tee, Then install a 1-1/2"
long.l” NPT nipple in Tee with a Г NPT pipe cap to

complete drip leg.

3.

When using black iron gas pipe, install an A.G.A.

listed ground joint union between drip leg (sediment

trap) and furnace gas control. Locate ground joint

union to allow easy servicing of burner assembly
and gas control.

4.

Install gas pipe to inlet side of furnace gas control.

WARNINGS

Do not thread gas pipe too far. Do­

ing so may cause gas control to split or crack

which could cause a gas leak or distortion or

malfunction of gas control. Thasa could causa a
firs or explosion resulting in damage, Injury or
death.

5.

Isolate gas control from gas supply line pressure

during leak check. Gas supply line test pressure de­

termines how you isolate gas control.

WARNINGS

At gas supply line, test pressure

equal to or less than 14 Inches W.C. (1/2 PSI).
Isolate gas control from gas supply line by turning
furnace gas control knob clockwise > to off posi­

tion. Unexpected surges could damage gas con­
trol causing gas to leak, resulting In firs or ex­
plosion.

WARNINGS

When test pressure la above 14

Inches W.C. (1/2 PSI), completely disconnect gas

control from gas supply line. Failure to Isolate

gas control from test pressure could damage H,

causing gas to leak, resulting in firs or explosion.

6.

Use a commercial soap solution made to detect leaks

and check all gas piping connections. Bubbles indi­

cate gas leakage. Seat all leaks before proceeding.

WARNINGi

Never use an open flams to check

for gas leaks. If a leak doss exist, a firs or explo­
sion could occur, resulting In damage. Injury or

death.

Furnace Gas Entry Piping.

1. See below for gas entry holes and knockouts.

a.

A 1-1/4*

X

2-3/4" knockout

in

top plate.

b. A 1-1/2" diameter hole and a 1-1/4" x 1-15/16"

knockout in right side of casing.

c.

Two 1-5/8" diameter knockouts in left side of
casing.

2.

Changing Gas Control Inlet.

You may want to change direction of gas inlet elbow
on gas control. Gas control is shipped for right side
gas entry. If you need top entry, remove the fitting. If
you need left side gas entry, rotate the fitting 180
degrees.

18