a.

Use 9/64" Hex Allen wrench to remove tour

screws. Check that O-ring is in bottom of gas
inlet elbow. Rotate elbow to desired position.

b.

Alternately tighten tour screws to 45 inch pounds

to form a gas tight seal.

c.

Use a commercial soap solution made to detect

leaks and check all gas piping connections.
Bubbles indicate gas leakage. Seal all leaks be­

fore proceeding.

WARNINOi

Never use an open flame to

check for gas leaks. If a leak does exist, a
fire or explosion could occur, resulting In
damage, Injury or death.

3.

Allowing tor Electronic Air Cleaners.

Some large electronic air cleaners will interfere with
incoming gas line. Install air cleaner on opposite fur­
nace side from gas entry or route gas pipe over top
of air cleaner through one of alternate knockouts.

SICTION 12 —
INSTALLING ILICTRICAL WIRING.

Equipment Needed: Save time by getting these tools before

you start: Item number(s) 2 listed in Section 10.

Select a location for room thermostat that is away from sup­
ply and return air registers, on draft-free interior wall, and not
near lights, television, direct sunlight, or other heat sources.

Install thermostat following field wiring diagram in Section
13. Use electrical wiring that meets current National Electrical

Code ANSI/NFPA 70 and local codes. Use Type T (63 de­
grees C rise) wire or equivalent. See Section 30 for code
information.

WARNINGi

Provide furnace with ita own separate elec­

trical circuit, means of circuit protection and electrical
disconnect switch. Follow current National Electrical Code
ANSI/NFPA 70 and state and local codes. Failure to pro­
vide these shut-off means could cause electrical shock

or fire, resulting In damage, Injury or death.

install proper electrical grounding by attaching grounding
source to green wire conductor in furnace junction box. Fol­
low current National Electrical Code ANSI/NFPA 70 and local

codes.

WARNINGS

Furnace must have proper electrical ground.

Failure to provide a proper electrical ground could cause
electrical shock or fire, resulting In damage. Injury or
death.

fICTION 13 —
FOLLOWING FIELD WIRING DIAGRAM

HEATING COOUNG

THERMOSTAT MODEL

TO 115V 1 PH 60 H2

POWR SUPPLY PER

LOCAL CODES

FIELD WIRING DIAGRAM

FIGURE 21

NOTE: When replacing original wire, use same type, color,

or equivalent wire. Remember to renumber wire ends.

SECTION 14 — ADJUSTING ROOM
THERMOSTAT HEAT ANTICIPATOR

Equipment Needed: Save time by getting these tools before

you start: Item number(s)5,17 and 18 listed in Section 10.

Wire system using field wiring diagram in Section 13.