Horizontal termination, 90° h – Continental BCDV48N User Manual

Page 11

Advertising
background image

W415-0327 / B / 12.07.07

11

V

1

HORIZONTAL TERMINATION

See graph to determine the required
vertical rise V

T

for the required hori-

zontal run H

T

.

For vent confi gurations requiring more than one 45º and 90° elbow
the following formulas apply:

Formula 1: H

T

< 4.2 V

T

Formula 2: H

T

+ V

T

< 24.75 feet

FIGURE 8

REQUIRED
VERTICAL
RISE IN
INCHES (V

T

)

HORIZONTAL VENT RUN PLUS OFFSETS IN FEET

when (H

T

) > (V

T

)

Simple venting confi guration (only one 45º and 90° elbow)

Example 2:

V

1

= 4 ft

V

2

= 1.5 ft

V

T

=

V

1

+ V

2

= 4 ft + 1.5 ft = 5.5 ft

H

1

=

2

ft

H

2

=

1

ft

H

3

=

1

ft

H

4

=

1.5

ft

H

R

=

H

1

+ H

2

+ H

3

+ H

4

= 2 + 1 + 1 + 1. 5 = 5.5 ft

H

O

= .03 (one 45º elbow + four 90º elbows -135º)

=.03

(405-135)=8.1ft

H

T

=

H

R

+ H

O

= 5.5 + 8.1 = 13.6ft

H

T

+ V

T

= 13.6 + 5.5 = 19.1 ft

Formula 1:

H

T

< 4.2 V

T

4.2

V

T

= 4.2 x 5.5 = 23.1 ft

13.6 < 23.1

Formula 2:

H

T

+ V

T

< 24.75 feet

19.1

<

24.75

Since both formulas are met, this vent confi guration is ac-
ceptable.

H

4

90°

H

3

H

1

90°

H

2

90°

FIGURE 9

45°

The shaded area within the lines represents acceptable values
for H

T

and V

T

.

V

2

90°