12 vertical termination, 90° v – Continental BCDV48N User Manual

Page 12

Advertising
background image

W415-0327 / B / 12.07.07

12

VERTICAL TERMINATION

Example 3:

V

1

= 5 ft

V

2

= 10 ft

V

T

= V

1

+ V

2

= 5 + 10 = 15 ft

H

1

=

3

ft

H

2

=

2.5

ft

H

R

=

H

1

+ H

2

= 3 + 2.5 = 5.5 ft

H

O

= .03 (one 45º elbow + three 90º elbows - 135º)

=

.03(45+90+90+90-135)=5.4

H

T

=

H

R

+ H

O

= 5.5 + 5.4 = 10.9 ft

H

T

+ V

T

= 10.9 + 15 = 25.9 ft

Formula 1:

H

T

< V

T

10.9 < 15

Formula 2:

H

T

+ V

T

< 40 feet

25.9

<

40

Since both formulas are met, this vent confi guration is ac-
ceptable.

when (H

T

) < (V

T

)

Simple venting confi gurations

FIGURE 10

REQUIRED VERTICAL RISE
IN FEET (V

T

)

HORIZONTAL VENT RUN PLUS
OFFSETS IN FEET (H

T

)

FIGURE 11

For vent confi gurations requiring more than one 45º and one 90°
elbow , the following formulas apply:

Formula 1: H

T

< V

T

Formula 2: H

T

+ V

T

< 40 feet

See graph to determine the required vertical rise V

T

for the required

horizontal run H

T

.

90°

90°

V

1

H

1

H

2

V

2

45°

45°

90°

The shaded area within the lines represents acceptable values
for H

T

and V

T

.

Advertising