Rs-232/rs-485 serial ports, Rs-232/rs-485 serial ports -6 – Echelon i.LON 100 e2 Internet Server User Manual

Page 20

Advertising
background image

2-6

Mounting, Cabling and Connections

• High voltage mains power;
• Dry contact relay outputs;
• Pulse meter inputs;
• Digital inputs;
• L

ON

W

ORKS

network;

• +12V < 20mA Output;
Each of these groups is described in detail below.

RS-232/RS-485 Serial Ports

The i.LON 100 includes one isolated RS-485 multi-drop bus port and one EIA-232
serial port. These ports can be used to connect the i.LON 100 to a GSM modem,

to other computers, or to bus systems. To connect the i.LON 100 to a GSM

modem, the serial connector from the modem must be attached to the ports on
the i.LON 100 as shown in the following table:

i.LON 100 Server GSM Modem Connections

GSM Modem DB

9 Pin

i.LON 100 Screw

Terminal

Enclosure Marking

1 not

connected

N/A

2 pin

23

RXD

3 pin

24

TXD

4 not

connected

N/A

5 pin

25

GND

6 not

connected

N/A

7 pin

21

RTS

8 pin

22

CTS

9 not

connected

N/A


If the RS-485 and EIA-232 ports are physically connected to a device other than a

GSM modem or an M-Bus device, a special custom software driver must be
provided by Echelon to support the intended application and enable

communications over the port (check the Echelon website (www.echelon.com) for

availability).
The EIA-232 serial connections are implemented on screw terminals 21 through

25. To connect a GSM modem to the i.LON 100 RS-232 port, a cable may be
ordered in Europe from EBV. The part number is ECH-RS232/500.
The RS-485 bus connections are implemented on screw terminals 26 though 28.

These are polarity sensitive signals and the (+) and (-) connections are noted
adjacent to the terminals. Since RS-485 is susceptible to common mode ground

differential voltage swings, it is imperative that a suitable shielded cable be used

when connecting RS-485 based devices. Reversing the polarity of the RS-485 bus
will cause improper bus operation and must be avoided.
In order to connect M-Bus devices to an i.LON 100 device, a level converter is

needed. This level converter is connected to the RS-232 interface of the i.LON
100 and to the M-Bus devices. It not only converts the M-Bus signals to RS-232