Echelon i.LON 100 e2 Internet Server User Manual

Page 65

Advertising
background image

i.LON 100 Internet Server User’s Guide

4-23

Driver from the drop-down menu. The M-Bus Driver Web page opens, as

shown in the following figure:

3. Click

the

Add button. A new M-Bus device is added to the page, as shown in

the following figure:

4. Enter the following information:


Name

The name of the data point to be associated

with the M-Bus device. Once a name has been

assigned (i.e. the Submit button has been
clicked), it cannot be changed. This name can

be up to 30 characters long and must begin with
“MBS_”. The “<”, “>”, and “&” characters may

not be used in this name.

Address

Choose primary (Pri) or secondary (Sec)

addressing mode. An M-Bus device contains
both a primary address and a secondary

address. The primary address is assigned by
the network management tool used to install

the M-Bus device (analogous to a L

ON

W

ORKS

subnet/node address); the secondary address is
burned into the device at the factory (analogous

to a L

ON

W

ORKS

Neuron ID).

Primary

This field is only active if Address is set to Pri.
Enter the primary address of the M-Bus device.

Valid range is 0 to 255.

Secondary

This field is only active if Address is set to Sec.

Enter the secondary address of the M-Bus
device. Valid range is 0 to 99,999,999.

Baud Rate

Select the baud rate at which the M-Bus device

communicates on the serial port. The default is

2400 bps. See the documentation for your M-
Bus device for more information on supported

baud rates.

Poll Rate

The poll rate for the device, in seconds. The M-