ENMET MX-32 User Manual

Page 19

Advertising
background image

MX32 E

NGUARD

ENMET Corporation

15

Manual alarm clearing:

If the gas content drops below the preset alarm threshold again this alarm must be cleared

manually by pressing the + (clear alarm) switch.

Automatic alarm clearing:

If the gas content drops below the pre-set alarm threshold again the relay will be

automatically cleared.

8. Press + or – to select manual (MAN) or automatic (AUT) mode for alarm clearing. Press ENTER

Press + or – to
select alarm clear
mode

35

MAN

1

Press ENTER when
correct alarm clear mode
is selected

00.05

man

1

Next the relay delay
time (in minutes) is
flashing

When the alarm threshold is exceeded the time delay is counted down then the alarms (buzzer and LED) are activated
the relay is activated. Use a 0 min setting for an instantaneous relay activation, this may cause nuisance alarms.

9. Press + or – to select time delay (in minutes) for alarm 1 relay. Press ENTER

Press + or – to
modify the time
digit by digit

00.05

min

1

Press ENTER when
correct time is selected

100

man

2

Next alarm AL2
threshold will be
flashing

10. This display indicates the Alarm threshold 2 and manual clearance. The red LED for the corresponding alarm is lit.
To modify the alarm threshold AL2 if necessary, Press + to change digit value and ENTER to move to next digit.

Press + or – to
modify the alarm
digit by digit

100

Ppm

2

Press ENTER when
correct threshold is
selected

100

man

2

Next the increasing
decreasing indicator is
flashing

11. Press + or – to select increasing or decreasing alarm type. Press ENTER

Press + for increasing
Press – for decreasing

100

man

2

Press ENTER when
correct alarm type is
selected

100

man

2

Next the MAN or
AUT is flashing

N

OTE

: The change may or may not be indicated on the display.

Manual alarm clearing:

If the gas content drops below the preset alarm threshold again this alarm must be cleared

manually by pressing the + (clear alarm) switch.

Automatic alarm clearing:

If the gas content drops below the pre-set alarm threshold again the relay will be

automatically cleared.

12. Press + or – to select manual (MAN) or automatic (AUT) mode for alarm clearing. Press ENTER

Press + or – to
select alarm clear
mode

100

MAN

2

Press ENTER when
correct alarm clear mode
is selected

00.05

man

2

Next the relay delay
time (in minutes) is
flashing

When the alarm threshold is exceeded the time delay is counted down then the alarms (buzzer and LED) are activated
the relay is activated. Use a 0 min setting for an instantaneous relay activation, this may cause nuisance alarms.

13. Press + or – to select time delay (in minutes) for alarm 2 relay. Press ENTER

Press + or – to
modify the time
digit by digit

00.05

min

2

Press ENTER when
correct time is selected

00.05

min

Next the fault relay
time delay will be
flashing

14. Press + or – to select time delay (in minutes) for alarm Fault relay. Press ENTER

Press + or – to
modify the time
digit by digit

00.05

min

Press ENTER when
correct time is selected

1.00

min

Next the stabilization
time count down at start
up will be flashing