4. OPERATING GUIDE - DISCHARGING

4.7.2 NICKEL-CADMIUM BATTERY

Check each cell with a digital voltmeter near the end of the test.

A. If no cells have dropped below 1.0 volts at the end of the specified time the

battery has successfully completed the capacity test.

B. If any cells have dropped below 1.0 volt before or at the end of the capacity test

the battery must be reconditioned (deep cycled). Please refer to the battery

manufacturer's maintenance manual on how to proceed.

L. SWITCH AC POWER OFF.

Switch the AC on-off/reset switch off before

removing the battery.

NOTE: If in emergency it is required to

stop the test, switch the unit to off/reset.

When the test is restarted the timer is

reset to zero. It may be necessary to

recharge the battery before resuming the

test.