3. OPERATING GUIDE - CHARGING

The constant-current charge method can however be used for reconditioning

SLAB’s. The current must be set low and the timer set to 12-18 hours. The battery

should be periodically monitored for overheat during reconditioning. When the battery

begins to accept charge current, it can be switched to constant-potential charging set

to 14.5 (12 volt battery) or 28.6 volts (24 volt battery).

3.2.4 NICKEL-CADMIUM BATTERIES

Nickel-cadmium batteries may be initially charged with constant potential set to

14.5 (12 volt battery) or 28.6 (24 volt battery). After the initial charge the batteries

could be topped with a low constant-current (usually C

per cell.

1

/10) charge to 1.55 volts

The nickel-cadmium can also be completely charged in the constant-current mode.

The current would be adjusted to a lower rate for topping. A low constant current

applied during a long time can also be used to eliminate fading, previously called the

“memory effect”, from nickel-cadmium batteries.

Refer to your manufacturer’s maintenance manual for the recommended

discharge times.

3.3 PREPARATION FOR CHARGING

Before starting charging the battery, read the component maintenance manual

(CMM) or the operating and maintenance manual (OMM) for the specific battery.

Ensure that the charge time and current or voltage from the battery manufacturer

are followed.

It is recommended that a visual inspection of the battery is carried out in

conjunction with testing and charging batteries. The charging, unless otherwise

specified in the manufacturer's CMM/OMM, shall be conducted at room ambient

temperature of 70°F to 85°F (21°C to 29°C).

1.1.1 VERIFY END VOLTAGE

The end voltage (in all charge modes) can be verified by the following steps: 1)

turn unit power off; 2) disconnect any battery; 3) turn charge current to max; 4) turn

unit power on; and 5) verify the end voltages on the CA-1550 digital voltmeter (see

also Modify Constant Potential in section 3.5).

WARNING: Always turn the AC power switch off before

connecting or disconnecting a battery

NOTE: Once set, all settings are maintained and need not be

reset for duplicate charging

CA-1550 CHARGER / ANALYZER - OPERATING MANUAL V1.2