Unit display and interface, Inputs and outputs confi guration – WaterFurnace Series NXW User Manual

Page 25

Advertising
background image

25

ENVISION

2

NKW 50Hz REVERSIBLE CHILLER INSTALLATION MANUAL

Inputs and Outputs Confi guration

DUAL STAGE WW

Input Name

Input

Output Name

Output

Entering Load Water Temperature

AI 1

Compressor 1

DO1

Leaving Load Water Temperature 1

AI 2

Compressor 2

DO2

Source Heating Freeze Detection 1

AI 3

Reversing Valve

DO3

Source Heating Freeze Detection 2

AI 4

Accessory

DO4

Load Cooling Freeze Detection 1

AI 5

Compressor 1 Alarm

DO5

Load Cooling Freeze Detection 2

AI 6

Compressor 2 Alarm

DO6

Network Output

DO7

Load Flow Proving Switch

DI 1

Network Output

DO8

Emergency Shutdown

DI 2

Network Output

D09

Stage 2 Low Pressure

DI 3

Source Htg Freeze Detection Select - 1ºC

DI 4

Future

PWM1

Load Htg Freeze Detection Select - 1ºC

DI 5

Future

PWM2

Stage 1 Low Pressure

DI 6

Thermostat Y1

DI 7

Thermostat Y2

DI 8

Thermostat B

DI 9

Source Flow Proving Switch

D10

Stage 1 High Pressure

DI11

Stage 2 High Pressure

DI12

XP10 Expansion Card
Input Name

Input

Output Name

Output

Entering Source Water Temperature

AI 1

Unused

DO 1

Leaving Source Water Temperature 1

AI 2

Unused

DO 2

Current Switch 1 - Compressor 1

AI 3

Unused

DO 3

Current Switch 2 - Compressor 2

AI 4

Unused

DO 4

Unit Display and Interface

The Unit Display allows the user to view entering and leaving water temperatures, freeze detection readings, inputs and

outputs, and allows the user enable and disable certain control functions through the various menus. The interface also

displays all faults on the LCD once the unit has locked out to aid in diagnostics.

There are 10 LED indicator lights that indicate the following:

Power - Shows that the FX processor

is operational

Alarm - Lights when there is a

lock-out or faulty freeze

detection sensor

1 - Flashing shows Compressor 1

is running

2 - Flashing shows Compressor 2

is running

3 - On shows Compressor 2 is lead

4 - On shows Reversing valve in cool

8 - On shows unit in ‘Test’ mode

Figure 5 - Unit Display/Interface

Escape Key

Return Key

Directional Keys

LEDs

!