Unit display and interface cont, Menu and menu contents – WaterFurnace Series NXW User Manual

Page 27

Advertising
background image

27

ENVISION

2

NKW 50Hz REVERSIBLE CHILLER INSTALLATION MANUAL

Menu and Menu Contents

Alarm

• Displays unit alarms until the unit has been reset (Unit

alarms can be reset by holding both the Escape (ESC)

key and Return (

←) key for five seconds or by power

cycling the unit.)

Alarm History

If a fault occurs the fault will be recorded in history

viewable on the unit mounted display. Each fault type will

be displayed in the history menu with a number between

0 and 3. A reading of 3+ means that the fault has occurred

more than 3 times in the past. The history menu can be

cleared with a power cycle only. Alarm date and time are

not included in the history.

Unit Alarms

Unit alarms are shown on the display once the unit has

locked out.

Load Flow – Load Flow Switch is Not Closed

• The load flow switch must be closed prior to either

compressor starting and must remain closed for the

entire run time of the compressor(s).

Low Pressure 1 – Compressor Circuit 1 Low
Pressure Switch

• The low pressure switch is checked before compressor

start up and is monitored during compressor operation.

Src FP 1 Temp Low – Source Freeze
Detection Sensor 1

• The source freeze detection sensor on compressor circuit

1 has reached its setpoint.

Src FP 1 Sensor Bad

• The sensor for source freeze detection on compressor

circuit 1 is unreliable or is not reading.

LD FP 1 Temp Low – Load Freeze Detection Sensor 1

• The load freeze detection sensor on compressor circuit 1

has reached its setpoint.

LD FP 1 Sensor Bad

• The sensor for load freeze detection on compressor

circuit 1 is unreliable or is not reading.

Unit Display and Interface cont.

Source Flow – Source Flow Switch is Not Closed

• The source flow switch must be closed prior to either

compressor starting and must remain closed for the

entire run-time of the compressor(s).

High Pressure 1 – Compressor Circuit 1 High
Pressure Switch

• If high pressure switch 1 opens at any time during compressor

1 run time the compressor will be shut down immediately.

Low Pressure 2 - Compressor Circuit 2 Low
Pressure Switch

• The low pressure switch is checked before compressor

start up and is monitored during compressor operation.

Src FP 2 Temp Low - Source Freeze Detection
Sensor 2

• The source freeze detection sensor on compressor circuit

2 has reached its setpoint.

Src FP 2 Sensor Bad

• The sensor for source freeze detection on compressor

circuit 2 is unreliable or is not reading.

LD FP 2 Temp Low - Load Freeze Detection Sensor 2

• The load freeze detection sensor on compressor circuit 2

has reached its setpoint.

LD FP 2 Sensor Bad

• The sensor for load freeze detection on compressor

circuit 2 is unreliable or is not reading.

High Pressure 2 - Compressor Circuit 2 High
Pressure Switch

• If high pressure switch 2 opens at any time during compressor

2 run time the compressor will be shut down immediately.

Comp Start Failure – Compressor Start Failure

• If either compressor fails to start when the contactor pulls

in the compressor current switch will cause that compressor

to be locked out after 2 retries. The other compressor will

continue to operate normally in this condition.

Advertising