Nkw start-up form – WaterFurnace Series NXW User Manual

Page 37

Advertising
background image

37

ENVISION

2

NKW 50Hz REVERSIBLE CHILLER INSTALLATION MANUAL

Start-up Date

Unit Model #

Size:

Unit Tag #

Unit Serial #

Start-up Company

Start-Up Mode

Employee Name

Cooling / Heating

Job Name

Electrical Data

Voltage across L1-L2

Voltage across L2-L3

Water Side

Balance Complete

Voltage across L1-L3

YES / NO

Circuit 1

Circuit 2

208/230V Transformer

Configuration

Compressor Amps (Red Wire)

208

230

Compressor Amps (White Wire)

380/420V Transformer

Configuration

Compressor Amps (Black Wire)

380

420

Circuit 1

Circuit 2

Antifreeze Installed

(Select)

Thermistor Checks,

Prior to Starting

Compressors

Entering Load Water Temperature

with no Compressors running

Load

Source

Leaving Load Water Temperature

with no Compressors Running

None

Prop. Glycol

Methanol

Ethanol

None

Prop. Glycol

Methanol

Ethanol

Entering Source Water Temperature

with no Compressors running

Leaving Source Water Temperature

with no Compressors running

Freeze Protection

Setpoint in The MUI.

Source Freeze Temperature

Water Flowing thru unit only

(No compressors on)

LOAD

SOURCE

Load Freeze Temperature

Water Flowing thru unit only

(No compressors on)

0.5° / -9.4°

0.5° / -9.4°

Compressors

Energized

Entering Load Water Temperature

Fluid Samples Taken

Leaving Load Water Temperature

LOAD

NO / YES

SOURCE

NO / YES

Entering Source Water Temperature

Antifreeze Concentration (%)

Leaving Source Water Temperature

LOAD

SOURCE

Evaporator/

Condenser Flow

Analysis

Entering Water Pressure on

Source Heat Exchanger

Source Flow Rate

(L/S)

Leaving Water Pressure on

Source Heat Exchanger

Entering Water Pressure on

Load Heat Exchanger

Load Flow Rate

(L/S)

Leaving Water Pressure on

Load Heat Exchanger

Circuit 1

Circuit 2

Refrigerant

Thermistors,

Compressors

Running

Source Freeze Temperature

Load Freeze Temperature

General Notes

NKW Start-Up Form